background image

Ancillary
Items

Gilberts range of ancillary Items have been designed for use in conjunction with both the Ductgard and Smokegard models.
Purpose built for straightforward connection and compatibility they offer a number of useful services.

Remote Indicators/Master Monitors

Gilberts remote indicator panels can be linked to
damper Modes 5 and 6 and will provide remote
indication of the status of one or more dampers.
Ref:- 

RT1 (1 damper)
MM1-12 (upto 12 dampers)
Larger Panels available upon request

Standard Power Supply

Standard power supplies are available in two
sizes to suit up to 6 or up to 12 dampers. They
provide conversion from 240v AC input to a
smooth and stabilised 24v DC output.
Ref:- 

G6 = 6 UNIT OUTPUT
G12 = 12 UNIT OUTPUT
G6R = 6 UNIT  RELAY
G12R = 12 UNIT  RELAY

Uninterruptible Power Supply

Uninterruptible power supplies operating on a
240v AC input provide a smooth 24v DC output to
power up to 12 dampers. Unlike standard power
supplies however, in the event of a power failure,
there will be an automatic changeover to in-built
batteries without tripping the dampers providing
continued power for a period of up to 1 hour.
Ref:- 

UPS6 = 6 UNIT OUTPUT
UPS12 = 12 UNIT OUTPUT
UPS6R = 6 UNIT  RELAY
UPS12R = 12 UNIT  RELAY

Smoke Detectors

Smoke Detectors are available for in duct or ceiling mounting and can link directly into Modes
5 & 6 or the output relay of the Power Supply units. Detectors are 24v DC Ionisation type
Ref:

In-duct 4 wire -

SD3

4 wire - 

SD2

RED LIGHT

SYSTEM TRIPPED

GREEN LIGHT

SYSTEM SET

UNIT No.

AIIFA No.

OUTLINE OF PCB

NOTE: When damper is open yellow is +VE
            When damper is closed blue is +VE

O
R

G

YELLOW

BLUE

-VE DC

FROM

DUCTGARD

100mm

76mm

35mm

240mm

240mm

87mm

POWER SUPPLY

UNIT

TYPE G12

MAINS INPUT 240 V.A.C.l

OUTPUT TO DAMPER 24 V.A.C.l

WARNING - ISOLATE

MAINS SUPPLY BEFORE 

ENTERING

E
N
L

MAIN POWER SUPPLY
240v AC

24v DC POWER OUT

240mm

350mm

87mm

UNINTERUPTABLE 

POWER SUPPLY

CELLS:- 27.6v DC MAX: TEST YEARLY

MAINS INPUT: 240v AC
OUTPUT TO DAMPERS 24v DC

ON
ON

THIS UNIT IS DESIGNED TO SUPPLY UP 

TO 12 DAMPERS FOR UP TO 1 HOUR

THE INTERNAL DRY-FIT CELLS DO NOT REQUIRE SERVICE OR 

ELECTROLYTE LEVEL TOPPING-UP. WARNING: TAKE CARE WHEN 

INSIDE THIS UNIT CELLS GIVE 100+ AMPS IF SHORTED OUT

E
N
L

MAIN POWER SUPPLY
240v AC

24v DC POWER OUT

Master Monitor

A more advanced form of remote indication is
available with a master monitor. This unit
provides remote indication for the status of up to
12 individual dampers.
Ref:- MM1-12* 
* dependant on number of dampers on the
system

Master Monitor

UP TO 12 PCBs IN 1 

MASTER MONITOR

NOTE: When damper is open yellow is +VE
            When damper is closed blue is +VE

FROM

DUCTGARD

YELLOW

BLUE

-VE DC

O
R

G

O
R

G

240mm

240mm

87mm

12

Содержание DUCTGARD

Страница 1: ...and frame side seals Unique patented precision blade linkage mechanism 8 Different modes of operation Connections to suit most proprietary duct work Extensive range of external control facilities DUCTGARD Duct Mounting Smoke and Fire Control Dampers Dampers 1 NOV 2012 ...

Страница 2: ...f HVAC ductwork Developed from our well proven door mounting smokegard damper over 40 years of engineering experience in the industry and considerable ingenuity has been applied in the design and construction of this product to produce a damper of high efficiency reliability durability and ease of use INTRODUCTION ...

Страница 3: ...ailable as standard upon request Mode Description Page 5A Fully automatic electronic 24v DC opening with fail safe spring 4 closure via 72 C electro thermal link release 5B Fully automatic electronic 240v AC opening with fail safe spring 4 closure via 72 C electro thermal link release 6A Fully automatic electronic 24v DC closure with fail safe spring 4 opening via 72 C electro thermal link release...

Страница 4: ...incorporate a fishtail edge detail which with the help of the precision single rack operation enables the blades to close and interlock extremely tightly This provides a tough effective screen against smoke and flames for its maximum 4 hour rating Stainless Steel Edge Seals These provide effective barriers to cold smoke penetration and allow the blades to expand under fire conditions minimising le...

Страница 5: ...dication L E D and test facility The test key facility allows local checks to be made on the damper operation The L E D provides the following diagnostic checks GREEN DISPLAY Power supply ON unit set RED DISPLAY Power supply ON but unit in fail safe mode NO DISPLAY Power supply failure unit in fail safe mode The control box also provides an interface for remote status indication smoke detectors an...

Страница 6: ...ectro thermal fusible link which will fail at a pre determined temperature 72 C standard and close the damper irrespective of the status of the motor An integral test pushbutton on the electro thermal fuse housing allows for the local testing of the damper operation Motor Control Options A 24V AC or DC supply B 240V AC supply Note All options are complete with position microswitches as standard Re...

Страница 7: ...r self tapping into ductwork system List Size Range 200 1000 Diameter in 100mm increments For other circular duct sizes overall sizes as next size up standard size For example 315 duct has 312 spigots and 432 high casing Dim A Modes 9 10 140 Above with terminal box 240 Modes 5 6 240 Square and Rectangular Spigots Ref S Smaller and intermediate sizes available Circular Spigots Ref C Smaller and int...

Страница 8: ...ation where a damper larger than 1000mm x 1000mm is required multiple unit assemblies can be provided These can take the form of either a two pack horizontal or vertical assembly or a full 4 pack assembly i e two double assemblies Each module of the assembly is provided with its own control unit and fusible link Note Before installation of any multiple assembly proposed arrangements should be agre...

Страница 9: ...may be provided and fitted to a double module assembly not exceeding an overall size of 1524 x 1016mm split on the larger dimension Adjacent frame assemblies must be separated by builders work of a minimum distance of 225mm between installation frame upstand flanges unless approval has been previously obtained from the appropriate authority Where two fire dampers or two double module assemblies ar...

Страница 10: ...ding extra feature options Removal of the lid on the damper control box provides access to an internal terminal block for the following wiring connections If in doubt ask Modes 5 6 Control Option A Modes 5 6 Control Option B Standard Wiring Arrangement with Remote Indicator Option O G R L G R N 240VAC 9VA Supply 24VDC 300MA Supply O G R G R switch or volt free contacts O G R L G R N 240VAC 9VA Sup...

Страница 11: ...e available upon request 1 2 M Control Option A 1 2 M Control Option B S1 S2 S3 S4 S5 S6 5 80 S1 S2 S3 S4 S5 S6 5 80 L N E M N L 1 2 3 4 5 6 S S 1 2 3 4 5 6 2 Core Screened Communication Cable Belimo Damper Motor DCM Damper Control Module 240V 50HZ Fused Spur option 24V DC 24 V WIRING DIAGRAM Power Supply 24V AC 20 50 60 Hz 24V DC 20 Current Rating 380mA AC max POWER CONSUMPTION Opening 5 watts Ho...

Страница 12: ...ressable module has been designed to provide independent operation of individual or groups of dampers in accordance with a pre programmed logic sequence of events Individual dampers are controlled and have there status constantly monitored by the module in response to signals from the pre programmed controller Maximum length of communications 2km In the event of communications failure dampers assu...

Страница 13: ...oke Detectors Smoke Detectors are available for in duct or ceiling mounting and can link directly into Modes 5 6 or the output relay of the Power Supply units Detectors are 24v DC Ionisation type Ref In duct 4 wire SD3 4 wire SD2 RED LIGHT SYSTEM TRIPPED GREEN LIGHT SYSTEM SET UNIT No AIIFA No OUTLINE OF PCB NOTE When damper is open yellow is VE When damper is closed blue is VE O R G YELLOW BLUE V...

Страница 14: ...time there were not any significant gaps in or around the assembly to permit the passage of flames Air Velocity Against Pressure Drop The graph opposite has been formulated to give an indication of the pressure drop expected through a fully open damper in relation to duct air velocity Airflow Blade Leakage Against Differential Pressure The graph opposite illustrates the maximum leakage obtainable ...

Страница 15: ...ve linkage motors and electronic components on the ductgard units are sealed for life there should be no requirement for periodic maintenance and spares are not normally required Items such as reset levers and test keys however can be misplaced over time In this event replacements are readily available from Head Office Trouble Shooting Gilberts Damper Smoke and Fire Control Range All Ductgard unit...

Страница 16: ...h return edge channels for retaining the top and bottom seals Damper Blades The damper blades are made from 0 45mm thick 018 BS 1449 stainless steel Blades are formed into a hollow sectional profile The blade ends are formed into individual circular drive shafts and located on brass bushes through the side channels Side seals of 0 25mm stainless as per blade specification are formed and pierced to...

Отзывы: