Giersch GIEGA NTG Скачать руководство пользователя страница 11

11.

  CONTENTS OF PACKAGE 

SUPPLIED 

  The following parts are supplied: 

  Boiler body -mounted, tested and complete with doors and 

accessories 

  Jacket and insulation 

 Front 

door 

 Control 

panel

 

12.

 INSTALLATION 

(Fig. 4)

 

The boiler must be installed by a properly qualified person. It 
must be installed in a room of a suitable size in compliance with 
the relevant safety rules. 
The plumbing system must ensure a minimum flow of water into 
the boiler as shown in the specification. Figure 5 shows two 
examples of plumbing system layout. If a sealed expansion tank 
is used, a safety valve must be fitted. Always remember to 
comply with any local rules on the safety of heating systems.  

LEGEND  

1 –Open expansion tank 
2 –Pump 
3 –One-way valve 
4 -Re-circulation pump 
5 –Return 
6 –Delivery 
7 –Heating shell 
8 –Sealed expansion tank 
9 –Filling valve 
10 –Safety valve

 

13.

  HOW TO INSTALL THE BOILER 

The boiler is installed in separate stages: 
1.  Assembly of the jacket. 
2.  Plumbing connections and hydraulic test. 
3.  Installation of the control panel.

 

PRELIMINARIES 

(Figs. 5-6-7)

 

a)  Take the boiler, still on its pallet, near the place where it will 

be installed; 

b)  Mount the four feet (40) with the four screws M8x35 (41) and 

the four nuts M8 (42); 

c)  Screw in the four screws M12 (43); 
d)  Remove the boiler from the pallet; 
e)  Push the boiler to the place where you want to install it. 

13.1 – JACKET ASSEMBLY 

(Figs. 8-9-10-11-12)

  

1.  Mount the brackets (22, 24) on the front element (21) and 

lock them with flanged nuts M10 (8). 

2.  Cover the boiler shell with layer of insulation (38) making 

sure is centred and adheres properly. 

3. Fit the insulating panel (37) onto the rear element, 

centring the holes in the tie-rods (3). 

4. Mount the rear panel (39), centring the holes in the tie-

rods (3). 

5.  Mount the side panels (31, 34) of the jacket. 
6.  Lock the side panels onto the brackets (22, 24) and to the 

rear panel (39) using the screws (32). 

13.2 -  PLUMBING CONNECTIONS AND 

HYDRAULIC TEST 

(Figs. 3)

  

Always clean the system completely before making the plumbing 
connections. 
1.  Mount a ½" cock (C) to drain the boiler. 
2.  Connect the delivery and return pipes using 1" 1/4 the 

threaded fittings on the rear elements for the heating circuit. 

3.  Fill the boiler slowly and relieve it entirely of air. Charge the 

system until the pressure is at least 1 bar.  

CAUTION!

 The maximum working pressure is 4 bar.

 

 

13.3 -  CONTROL PANEL INSTALLATION 

(Figs. 2-13-14-15-16-17-18)

 

1)  Secure the control panel (51) onto the instrument 

support (50) using the four screws (52) 

2) 

Unwind the capillaries of the thermostats (44, 46) and 
the thermometer (49). Insert the probes in the sheath 
(19) and tighten them with the probe retaining spring. 

CAUTION!

 When unwinding the capillaries, be very careful not 

to create sharp bends or twists.  

3) 

Mount the complete control panel onto the side panel (31, 
34) centring the holes and secure it with the two screws 
(36).  

4) 

Connect the cable of the power supply, insert this in the 
wire lead and lock this in position. Refer to paragraph 14. 
WIRING for further details. 

CAUTION! Connect all earthing cables to the screw.  

5) 

Mount the electric protection panel (48) has indicated in the 
picture 16. 

6) 

Lastly, mount the top panel (35) and the front panel (33) in 
that order.

 

7) 

Stick the rating plate on to the right-hand side panel (31) of 
the jacket.

 

14.

 WIRING 

(Figs. 2)

 

The boiler must be have a single-phase power supply 220/230V, 
50Hz plus earth (  ) connected to terminals N and L.  

CAUTION! Respect PHASE-NEUTRAL polarity!  

Key to symbols: 
T.R. =  Boiler setting thermostat (44) 
T.S. =  Safety thermostat (46) 
B.R. =  Burner 
S.     =  ON/OFF Switch (45) 
F.     =  Fuse (47)

 

15.

  CONNECTING TO THE STACK

 

Check that the dimensions and the status of the stack (parasite 
air inlets, obstructions, etc.) are suited to the performance of the 
boiler. 
The cross section and height of the stack must ensure the 
minimum draft as specified in the table for each model.
Proceed as follows: 

  Connect to the rear element. 

  Use a tube with a diameter that is at least the same as for the 

exhaust pipe. 

  Reduce the number of bends and avoid sharp changes of 

direction. 

  Make sure there is at least 5% angle of inclination for the pipe 

and insulate it if necessary. 

  Check the seal of the fittings. 

16.

 INSTALLING THE BURNER 

(Fig.1)

 

The lower cover (10) has a burner flange corresponding to the 
one shown in Fig. 1. If the burner flange is not suited to this 
flanging, an adapter and gasket must be provided. The diameter 
of the burner head may differ from the diameter of the insulation. 
If it is larger, widen the insulation hole. If it is smaller, add 
insulation to adapt the hole ad accurately as possible to prevent 
backfiring. The maximum diameter allowed is 110 mm. It is 
advisable to graphitize the burner screws to facilitate removal 
later on. 

17.

 REGULATING THERMAL 

POWER

 

The boiler's thermal power must be regulated according to the 
requirements of the system. Read the burner instructions very 
carefully and use nozzles and fuel pressure to get the required 
value.

 

Содержание GIEGA NTG

Страница 1: ...GIEGA NTG 24 75 kW GAS OR OIL BOILER INSTALLATION AND MAINTENANCE HANDBOOK 1312 1312AT2668...

Страница 2: ...44 46 49 45 47 18 15 20 10 14 12 27 C 20 1 A B max 110 45 N 4 M8 150 min 275 20 50 mm 1 7 6 2 3 4 5 6 7 2 3 10 8 5 4 9 47 Fig 1 Fig 2 Fig 3 Fig 4...

Страница 3: ...41 43 42 40 24 22 21 8 GIEGA NTG 24 33 43 24 21 8 22 GIEGA NTG 53 63 74 37 38 Fig 8 Fig 9 Fig 7 Fig 6 Fig 5...

Страница 4: ...39 3 31 32 39 34 24 32 GIEGA NTG 24 33 43 GIEGA NTG 53 63 74 32 24 34 51 50 52 Fig 13 Fig 14 Fig 12 A Fig 12 B Fig 10 Fig 11...

Страница 5: ...36 19 48 35 33 GIEGA NTG 24 33 43 35 31 33 35 31 GIEGA NTG 53 63 74 Fig 18 B Fig 17 Fig 18 A Fig 15 Fig 16...

Страница 6: ...1 2 3 17 7 10 13 14 2 28 29 25 17 6 11 12 4 15 16 25 25 26 26 26 5 2 6 7 2 2 30 17 19 20 21 23 27 18 GIEGA NTG Expl 1...

Страница 7: ...ake the ne cessary measures such as adding antifreeze or emptying the system 2 GENERAL DESCRIPTION Fig 1 This boiler which is made up of cast iron wet chamber elements and designed to operate with a v...

Страница 8: ...very large b only very hard water is available c for any reason the system has to be emptied partially or fully and then needs to be filled again 6 CONTROL PANEL Fig 2 The pre wired control panel com...

Страница 9: ...20 if in doubt Recommendations Check the pressure of the water in the system regularly The value shown on the gauge must not be less than 1 bar when cold Long stops Do not leave the boiler switched on...

Страница 10: ...8 22 30 32 45 60 Numbers of elements N 3 4 5 6 7 8 Boiler weight Kg 139 161 188 215 242 269 Width of boiler Mm Width of combustion chamber Mm 238 344 450 556 662 768 Volume of combustion chamber Dm3 1...

Страница 11: ...13 14 15 16 17 18 1 Secure the control panel 51 onto the instrument support 50 using the four screws 52 2 Unwind the capillaries of the thermostats 44 46 and the thermometer 49 Insert the probes in t...

Страница 12: ...rew M12x90 12 711208 Burner door insulation 44 Regulation thermostat 0 90 C 13 712025 Brass nut M10 45 ON OFF Switch 14 711217 Burner door insulation cord 46 Safety thermostat with manual reset 15 711...

Страница 13: ...GIEGA NTG 24 75 kW MANTEMENIOI 1312 1312AT2668...

Страница 14: ...1 2 1 3 4 5 1 EN 303 MANUFACTURER SERIAL NUMBER MODEL POWER...

Страница 15: ...E 89 336 CEE 90 C Boiler 2 4 2 diesel 1 4 E 20 C NHV 10210 kcal kl NHV 8570 kCal NM 3 2 5 20 25 F a b c 6 2 ON OFF 45 44 manual 46 49 44 44 7 2 max 4 bar 45 I 44 49 50 90 C 44 50 60 C 45 O BOILER C Fi...

Страница 16: ...8 2 3 10 15 3 5 27 14 20 12 18 14 20 1 BAR 100 g 1 2 46 3 44 1 2 3 4 5...

Страница 17: ...39 161 188 215 242 269 mm mm 238 344 450 556 662 768 Dm3 14 91 22 37 29 83 37 29 44 75 52 21 Dm3 21 83 31 82 41 72 51 66 61 50 71 52 L 14 6 18 2 21 8 25 4 29 0 32 6 mm 150 mm 150 153 Operating max pre...

Страница 18: ...12 43 d e 13 1 8 9 10 11 12 1 22 24 21 M10 8 2 38 3 37 3 4 39 3 5 31 34 6 22 24 39 32 13 2 3 1 C 2 1 1 4 3 1 BAR 4 R 13 3 2 13 14 15 16 17 18 1 51 50 52 2 44 46 49 19 3 31 34 36 4 14 5 48 16 6 35 33 7...

Страница 19: ...door insulation 44 Regulation thermostat 0 90 C 13 712025 Brass nut M10 45 ON OFF Switch 14 711217 Burner door insulation cord 46 Safety thermostat with manual reset 15 711782 Cleaning door with hinge...

Страница 20: ...711793 Installation and mainteinance handbook GIEGA NTG 24 75 01 04 07 rev 00...

Отзывы: