By the terminal M11it is possible to synchronize two control units, se
Connections:
Connect only one button START to one of the two control units.
Connect the photocell 1 to terminal 24 of one of the two control units. The command, by terminal M11, will be
extended also to the other control unit.
The radio plug-in receiver (if provided) can be connected to one of the two control units;
Connect possible devices more one by one on the control units as you would make on two separate systems.
Terminals legend :
S1 = start
S2 = photo 1
S3 = synchronism opens
S4 = common
In this application each control unit can be commanded one by one with OPEN, CLOSE and PEDESTRIAN
command.
The START command (external control panel or radio receiver) will enable both control unit.
To avoid any not synchronized movement, it is necessary to set :
Menu A3 = 4 (CONDOMINIUM LOGIC).
Menu C3 ( PREFLASHING ): the same on both control units.
If there are some photocells, menu C40=3 (terminal 24 set as PHOTOCELL 1) and connect them to terminal 24.
Menu C10 (HAMMER STROKE ): the same on both control units.
Menu E1 (TEST PHOTOCELL 1): the same on both control units.
Menu E3 (TEST SAFETY DEVICES): the same on both control units.
Menu E9 (RESERVE INPUT:, the same on both control units and parallel connections on both control units.
Menu H9: the same on both control units. The first central that starts the closing commands also the other one.
WARNING:
In case of intervention of safety devices (EDGE, STOP, PHOTOCELL 2 or MOTOR REVOLUTIONS SENSOR),
each control unit will be enabled one by one. They will be synchronized again at next manoeuvre.
e figure 31.
DESRCIZIONE MENU
( A )
19 - SYNCHRONISM
DESRCIZIONE MENU ( A )
20 - PEDESTRIAN MANOEUVRE
The pedestrian manoeuvre is made after the
channels plug-in receivers.
Operation in reply to PEDESTRIAN command:
Close gate
OPEN for the time set on menu H10 and till the opening limit switch max.
→
During opening
IRRELEVANT
→
Open gate
IRRELEVANT if the pedestrian automatic reclosing is enabled, otherwise
→
CLOSES
During closing
With menu E5=2 OPEN for the time set on menu H10 and till the opening limit
→
switch max.
With menu E5=1 OPEN completely.
→
closing of PEDESTRIAN contact (terminal 16) or by relay 2 of the two
DESRCIZIONE MENU ( A )
22 - FINAL CHECKING
Check the electrical connections: a wrong connection may damage both the control unit and the operator.
Check the correct position of the limit switches (MENU C23).
Always preset the mechanical stops in opening and closing.
Check the correct operation of photocells and safety devices.
Check that the motors are blocked and ready to work with GATE AT HALFWAY POSITION.
Remove possible obstacles in the operating area of the gate.
Check that the direction of gate motion is correct:
§
take off the power supply from the control unit.
§
power the control unit.
§
give a START command.
§
check that the gate is opening, otherwise take off the power supply rfrm the control unit and invert the wires of
terminal M2
Check the correct operation of the automation.
21 - RISING BOLLARD MODALITY (MENU A1=4)
In this modality it is necessary to use the additional control unit BX-6M (AS07010), for which you have to look up the
relevant manual for the connections.
The SC380 + BX-6M system allows to control up to six single-engine rising bollards or three twin-engined rising
bollards and allows to control all the rising bollards at the same time or only a group chosen by the switch SW1
present on BX-6M.
The signals Ped (terminal16), Reserve (terminal 21), Open (terminal 17), Close (terminal 18) assume the functions
shown in the table.
Signal
Effect
Reserve (terminal 21)
All the rising bollards open and will not close again automatically.
Ped (terminal16)
Open (terminal 17)
Close (terminal 18)
All the rising bollards close.
The rising bollards selected with switch Sw1 of th
open
and will not close again automatically.
e additional control unit BX-6M
The rising bollards selected with switch SW1 of the additonal control unit BX-6M
close.
The Start signal (terminal 15) keeps unaltered its function and operation settings (menu A3 and menu A5) and
enable all the rising bollards at the same time.