SC230
WARNING!
A programming of the function different from the configuration pre-set by the
manufacturer, although it allows, if correctly done, the reduction of the cases of stop of
the system in intermediate position (as a simply example, for the presence of frictions,
wind and/or obstacles on the way of the movable element), causes, in any case, a
reduction of the safety level of the same system and a consequent danger for people
safety.
10 - DIP SWITCH SW4
The settings are stored during the rest phase (gate closed).
The DEFAULT settings are coloured in grey
DIP 2
Electronic brake disabled.
OFF
ELECTRONIC BRAKE
ON
Description
DIP
Status
Function
DIP 1
Enables the function attempts after the intervention of the safety devices.
After the intervention of the safety device SAFETY or SAFETY-STOP (DIP 10 = ON) or
of the MOTOR RPM SENSOR and, after 10 seconds, the automation will try, for 3
times max., to restart the motion in the direction that has been interrupted.
After another intervention of the safety device, the automation stops waiting for some
commands.
ON
ATTEMPTS AFTER
SAFETY DEVICES
INTERVENTION
OFF
Disables the function.
SENS
Adjusts the intervention sensitivity of the motor rpm sensor .
Turning the trimmer clockwise, the sensitivity decreases.
11 - TRIMMER ADJUSTMENT
Trimmer
PAUSE
FORCE
SLOW
Description
Adjusts the PAUSE TIME from 2 to 220 seconds. The value is increased by turning the trimmer
clockwise.
Adjusts the motor FORCE/SPEED during the not decelerated movement period.
WARNING
: If the trimmer adjustment is less than 20% and according to the characteristics of
the system, it is possible that the gate stops before finishing its stroke.
Adjust appropriately the trimmer avoiding too low adjustments.
WARNING
: If the trimmer adjustment is less than 20% and according to the characteristics of
the system, it is possible that the gate stops before finishing its stroke.
Adjust appropiately the trimmer avoiding too low adjustments.
Adjusts the motor FORCE/SPEED level during the decelerated movement period.
Default
UK
15
Electronic brake enabled.
Activate this function when the gate shows excessive inertia or its movement exceeds
the limit switches.