II
User Notice
◆
When operating, the entire capacity of the cooperating indoor unit should be not
larger than 150% of outdoor unit. Otherwise, it will cause the shortage of cooling
(heating) capacity.
◆
The power supply of the entire unit must be the power supply of outdoor unit.
And disconnect the main power of outdoor units before cleaning.
◆
In order to turn on the units successfully, the main power switch should be
opened 8 hours before the operation.
◆
After receiving the turn off signal, every indoor unit will continue to work for
20-70sec to make use of the rest cool air or the rest heat air in the heat exchanger,
while preparing for the next operation. And this is normal.
◆
When the selected operating mode of the indoor unit are clash with the
operating mode of the outdoor unit, the malfunction light will blink after 5s on the indoor
unit or remote controller showing that the operation clash, then the indoor unit will stop.
At this time, change the operation mode of the indoor unit to the one that would not
clash with the outdoor operating mode to make the operation normal. The cooling mode
is not clash with the dry mode, while the fan mode is not clash with any mode.
◆
The appliance shall not be installed in the laundry .The appliance shall not be
used by children without supervisor.
◆
An all-pole disconnection switch having a contact separation of at least 3mm in
all poles should be connected in fixed wiring.
◆
Missing information regarding electric supply tole/-10%, +/-1Hz) in
documentation.
◆
Humidity range: 30%~95%.
◆
Main switch provided by end user: main switch handle should be black or gray,
it can be locked in ―OFF‖ position with padlock.
◆
The main disconnection device should be installed at a height of 0.6~1.7m.
over current protection is required(EN 60947-3, EN 60947-2).
◆
The cooling range of the unit is the outdoor environment temp.-5~48
℃
DB, the
heating range of the unit( only for the heat pump type unit) is the outdoor environment
temp. -15~27
℃
DB.
◆
This appliance can be used by children aged from 8 years and above and