Unitary Duct Split Unitary Duct Split
9
GWHD(36)NK3AO
Caution
!
①
. The incorrect of wiring connecting would lead malfunction of some of the
electric elements.
②
. Make sure that the lead between the connect end and the clamp end has some
need space after the wire is fixed.
③
. The appliance shall be installed in accordance with national wiring regulations.
5 Install the drainage pipe
Make sure the drain flows out
a. Drain piping.
*
The drainpipe outlet direction can be chosen from either the right rear or right.
*
The diameter of the drainpipe should be equal to or greater than the diameter of
the connecting pipe.
*
Keep the drain pipe short and incline downwards at a gradient of at least 1/100
to prevent air pockets.(Refer to Fig.10)
*
Use the attached drain hose
④
and clamp
⑤
.
*
Insert the drain hose completely into the drain socket. Tighten the clamp within
the range of gray tape until the screw head is less than 4mm from the hose. (Refer to
Fig.11,Fig.12)
*
Wrap the attached sealing pad over the clamp and drain hose to insulate.
(Refer to Fig.12)
*
No folding of drain hose inside the indoor unit. (Refer to Fig.13)
b. Confirm that smooth drainage is achieved after the piping work.
Pour 600cc of water into the drain pan from the air outlet for confirming
drainage.(Refer to Fig.14)