HD50CR-AS
- 21 -
V1.1
Address
Type
Holding Register description
10065
W
Buzzer silencing time, in minutes, for the quantity #1
10066
W
Buzzer silencing time, in minutes, for the quantity #2
10067
W
Buzzer silencing time, in minutes, for the quantity #3
10068
W
Buzzer silencing time, in minutes, for the quantity #4
10069
W
Buzzer silencing time, in minutes, for the quantity #5
10070
W
Buzzer silencing time, in minutes, for the quantity #6
10077
B
Current range of the analog output 1: 0=0…20 mA, 1=4…20 mA
10078
B
Voltage range of the analog output 1: 0=0…10 V, 1=0…5 V
10079
SW
Value of the quantity associated with the analog output 1 corresponding
to 0/4 mA and 0 V
10080
SW
Value of the quantity associated with the analog output 1 corresponding
to 20 mA and 5/10 V
10081
W
Analog output 1 test register: the current output goes to the value, in
tenths of mA, entered in the register (e.g., enter 120 for 12.0 mA).
Set -1 to exit the test mode.
10082
W
Analog output 1 test register: the voltage output goes to the value, in
tenths of V, entered in the register (e.g., enter 50 for 5.0 V).
Set -1 to exit the test mode.
10083
B
Current range of the analog output 2: 0=0…20 mA, 1=4…20 mA
10084
B
Voltage range of the analog output 2: 0=0…10 V, 1=0…5 V
10085
SW
Value of the quantity associated with the analog output 2 corresponding
to 0/4 mA and 0 V
10086
SW
Value of the quantity associated with the analog output 2 corresponding
to 20 mA and 5/10 V
10087
W
Analog output 2 test register: the current output goes to the value, in
tenths of mA, entered in the register (e.g., enter 120 for 12.0 mA).
Set -1 to exit the test mode.
10088
W
Analog output 2 test register: the voltage output goes to the value, in
tenths of V, entered in the register (e.g., enter 50 for 5.0 V).
Set -1 to exit the test mode.
10089
B
Current range of the analog output 3: 0=0…20 mA, 1=4…20 mA
10090
B
Voltage range of the analog output 3: 0=0…10 V, 1=0…5 V
10091
SW
Value of the quantity associated with the analog output 3 corresponding
to 0/4 mA and 0 V
10092
SW
Value of the quantity associated with the analog output 3 corresponding
to 20 mA and 5/10 V
10093
W
Analog output 3 test register: the current output goes to the value, in
tenths of mA, entered in the register (e.g., enter 120 for 12.0 mA).
Set -1 to exit the test mode.
10094
W
Analog output 3 test register: the voltage output goes to the value, in
tenths of V, entered in the register (e.g., enter 50 for 5.0 V).
Set -1 to exit the test mode.
10095
W
Period, in minutes, of the auto-calibration of the zero of the differential
pressure
da 20000
a 20011
B
User code with ASCII codification of the quantity #1.
da 20012
a 20023
B
User code with ASCII codification of the quantity #2.
da 20024
a 20035
B
User code with ASCII codification of the quantity #3.