5
2 Product description
The STL50 safety temperature limiter is used wherever thermal processes must be
monitored and the system must be switched to a safe operating state in case of a
fault. If the permissible temperature limit value is reached or an error occurs in the
monitoring device (probe break, probe short-circuit, failure of a component in the
device, error in the software, failure or impermissible value of the supply voltage,
etc.) within the permissible temperature range, the STL50 switches off immediately.
The alarm contact is confirmed, the front-side ALARM LED and the background
lighting of the display illuminate, and the cause of error is shown on the display in
plain text.
A 24 V DC signal for an external alarm is also connected to terminals 17-18.
2.1 Scope of delivery
Safety temperature limiter STL50 with packaging
This operating manual
2.2 Features
Can be used as
STB
Safety temperature limiter
ASTB
Exhaust gas safety temperature limiter
STW
Safety temperature monitor
Certified according to EN 61508 SIL2
Pt100 input, 3-wire connection or double thermocouple J, K, N and S
Programmable temperature limit value and switching hysteresis
Basic accuracy <0.5 %, ±2 digit
Reaction time ≤ 0,5 s
Alarm output 1 relay, SPDT
Pre-alarm output 1 relay, SPDT
Analog output 0/4 ... 20mA, 0/2 ... 10V
Memory function for error message
Operator lockout (password-protected)
Case for TS35 DIN rail mounting
Содержание STL50
Страница 7: ...7 2 5 Connection diagrams STL50 1 1R X 00 STL50 5 1R X 00 STL50 1 2RAO X 00 STL50 5 2RAO X 00 ...
Страница 25: ...25 9 Declaration of Conformity ...