Safety devices
X2: Door safety switch
The door safety switch is installed on the door and connected to the door control via the
spiral cable.
Menu "3.4":
Function type
Reaction upon activation
"1" Slack-wire / pedestrian door
Switch contact open: Door stops
Switch contact closed: Door ready for operation
"2" Crash switch as NC
Switch contact open: Door stops
Switching contact closed: Changeover to hold-to-run mode
With frequency Inverter: Door moves at crawling speed only
Resetting the error: Press the stop button of the door control
for 3 seconds
"3" Crash switch as NO
As function type "2"
Slack-wire / pedestrian door
If the switch is open circuit when an open or close command is given fault “F1.2” is displayed.
If activated during the door movement the door is immediately stopped and fault “F1.2” is
displayed.
Pass door switch: Entry sense
The switch tested to safety category 2 acc. to EN 13849-1 is monitored by the door control. If
the switch is open circuit when an open or close command is given fault “F1.2” is displayed. If
activated during the door movement the door is immediately stopped and fault “F1.2” is
displayed.