background image

9

GF U3000 V2 Ultrasonic Flowmeter

Modbus Supplement to the operating instructions

135

134

Flow Side 
Tempera-
ture

sint16

×100 ⁰C, ⁰F
e.g., 7557 = 75.57 ⁰C or ⁰F

R

Metric, Imperial

136

135

Return 
Side 
Tempera-
ture

sint16

×100 ⁰C, ⁰F
e.g., 3770 = 37.7 ⁰C or ⁰F

R

Metric, Imperial

137, 
138

136, 137

Status 
Flags

uint32

Update Primary Fwd Flow 
total:1

RW

Action/Response bit. 1=update; Reset to 
0 when complete.

Update Primary Rev Flow 
total:1

Action/Response bit. 1=update; Reset to 
0 when complete.

Update Primary Fwd Energy 
total:1

Action/Response bit. 1=update; Reset to 
0 when complete.

Update Primary Rev Energy 
total:1

Action/Response bit. 1=update; Reset to 
0 when complete.

Update Damping:1

Action/Response bit. 1=update; Reset to 
0 when complete. Uses values in 
Damping (Reg 135) and if dynamic 
damping is selected, the value of 
Dynamic Damping Acceleration 
Threshold (Regs 145,146)

Reserved:11

Reserved allocation of 10 MS bits of reg 
132

Reserved:13

Reserved allocation of 13 LS bits of reg 
133

Hot probe fault:1

Faulty or disconnected hot probe

Cold probe fault:1

Faulty or disconnected cold probe

Signal Loss:1

Device is online and has lost signal
E.g., Signal loss and Hot Probe Failure 
= 0b1010000000000000 = 0xC000

139

138

Damping

uint16

Damping Time:7
Damping Type:1
Reserved:8

RW

seconds
0=Fixed, 1=Dynamic

140

139

Q

uint16

Signal quality ×100

R

E.g., 94.3% = 9430 = 0x24D6

141

140

SNR

sint16

Signal to Noise ×100 in dB 

R

E.g., 53.7dB = 5370 = 0x14FA

142

141

Signal

sint16

Signal ×100 in dB

R

E.g., 42.53dB = 4253 = 0x109D

143

142

Gain

sint16

Gain ×100 in dB

R

E.g., 25.07dB = 2507 = 0x9CB

144

143

Noise

sint16

Noise ×100 in dB 

R

E.g., -11.7dB = -1170 = 0xFB6E

145, 
146

144, 145

ETA

IEEE754 SP

Estimated Time of Arrival in μS R

147,148 146, 147

ATA

IEEE754 SP

Actual Time of Arrival in μS

R

149,150 148, 149

Accelerati-
on 
Threshold

IEEE754 SP

Dynamic Damping Acceleration 
Threshold

RW

m/sec2, ft/sec2, ft/sec2,

151-200 150-199

Reserved uint16 x50

Not used.

RZ

Primary Flow Board. Reads zero. Not 
used. Future Expansion.

201-300 200-299

Reserved

RZ

Secondary Flow Board. Reads zero. Not 
used. Future Expansion.

Содержание U3000 V2

Страница 1: ...er 2026161 F U3000 V2 Modbus Supplement MA_00138 EN 00 07 2022 Georg Fischer Piping Systems Ltd CH 8201 Schaffhausen Switzerland 41 52 631 30 26 info ps georgfischer com www gfps com 7 Units 4 Velocit...

Страница 2: ...dentification 13 3 9 Status Flags 14 4 GLOSSARY 14 Original instruction manual Disclaimer The technical data are not binding It does not constitute expressly warranted characteristics and neither guar...

Страница 3: ...the next unit It is the responsibility of the user to install cable and wire to the MULTICOMP MP002510 Modbus plug connector The connection diagram is shown below in Figure 1 Note that the connection...

Страница 4: ...for the GF U3000 V2 Ultrasonic Flowmeter The Modbus specification for RTU mode defines an 11 bit character frame containing an 8 bit character If Parity is used then only one stop bit is required If...

Страница 5: ...ssages The following message types are supported from the Modbus Application Protocol Specification Message Type Message Number Notes READ HOLDING REGISTERS 03 0x03 Read a contiguous block of register...

Страница 6: ...of the mantissa are stored in the higher address Some registers below contain bit mappings These values may be manipulated via the MASK WRITE REGISTER command 22 as outlined in Table 1 Bit fields are...

Страница 7: ...value Interface version uint16 0x5A00 R This is a check value and an interface version number This version is zero All values start at the base 0x5A00 2 1 Device ID uint16 GF U3000 V2 Ultrasonic Flow...

Страница 8: ...12 MBM to control digital output s on a unit 12 100 Reserved uint16 Sec 6 RZ 0 to 59 101 102 100 101 Date Time uint32 Min 6 R 0 to 59 Hour 5 0 to 23 Day 5 1 to 31 1st 1 Month 4 1 to 12 Jan 1 Year 6 b...

Страница 9: ...d 13 Reserved allocation of 13 LS bits of reg 133 Hot probe fault 1 Faulty or disconnected hot probe Cold probe fault 1 Faulty or disconnected cold probe Signal Loss 1 Device is online and has lost si...

Страница 10: ...Registers Registers highlighted as RW are updateable They provide the ability to update the unit s configuration Except for the Regime regis ter register 5 offset 4 all updateable registers can be up...

Страница 11: ...lags associated with them Values can be written into these registers but no action will be taken until the associated flag is activated There are three key flags that must be considered when updating...

Страница 12: ...uint16 year month day hour minute second Read the time and date starting at register offset 8 timeNdate Read2HoldingRegisters 8 Extract elements second timeNdate mod 2 6 timeNdate timeNdate div 2 6 m...

Страница 13: ...address 136 with the AND mask being set to 0xFFEF and the OR mask being 0x0010 This will start the update 5 Send a MASK WRITE REGISTER message command 22 or 0x16 to register address 5 with the AND mas...

Страница 14: ...entry for the moment Status Flags Online The unit is currently reading flow This flag is reset when the unit stops reading flow and enters the configuration mode Status Flags Urgent Error An urgent er...

Страница 15: ...15 GF U3000 V2 Ultrasonic Flowmeter Modbus Supplement to the operating instructions...