GF U3000 V2 Ultrasonic Flowmeter

Modbus Supplement to the operating instructions

 

Three wire Weipu plug/

socket or block 

connector

U3000

U3000

U3000

G2.2  Recommended Modbus Network Toplogy

MODBUS CONFIGURATION

The Modbus board supplied with the GF U3000 V2 Ultrasonic Flowmeter complies with the Modbus Application Protocol Specification 
V1.1b3 and Modbus over Serial Line Specification and Implementation V1.02. Copies of these documents can be found at

https://modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf

and

https://modbus.org/docs/Modbus_over_serial_line_V1_02.pdf

respectively.

Only the mandatory RTU mode is supported for the GF U3000 V2 Ultrasonic Flowmeter.

The Modbus specification for RTU-mode defines an 11-bit character frame containing an 8-bit character. If Parity is used, then only 
one stop bit is required. If parity is not used, then two stop bits must be specified. In addition to the standard frame format, non-
standard 10-bit frames are also supported. In this case the GF U3000 V2 Ultrasonic Flowmeter will issue warnings but not prohibit 
the use of these formats.

The board supports the following baud-rate and parity combinations:

Baud Rate

Data Bits

Parity

Stop Bits

300

8

E, O, N

1, 2

600

8

E, O, N

1, 2

1200

8

E, O, N

1, 2

2400

8

E, O, N

1, 2

3600

8

E, O, N

1, 2

4800

8

E, O, N

1, 2

7200

8

E, O, N

1, 2

9600

8

E, O, N

1, 2

14K4

8

E, O, N

1, 2

19K2

8

E, O, N

1, 2

28K8

8

E, O, N

1, 2

38K4

8

E, O, N

1, 2

57K6

8

E, O, N

1, 2

76K8

8

E, O, N

1, 2

115K2

8

E, O, N

1, 2

230K4

8

E, O, N

1, 2

Содержание U3000 V2

Страница 1: ...er 2026161 F U3000 V2 Modbus Supplement MA_00138 EN 00 07 2022 Georg Fischer Piping Systems Ltd CH 8201 Schaffhausen Switzerland 41 52 631 30 26 info ps georgfischer com www gfps com 7 Units 4 Velocit...

Страница 2: ...dentification 13 3 9 Status Flags 14 4 GLOSSARY 14 Original instruction manual Disclaimer The technical data are not binding It does not constitute expressly warranted characteristics and neither guar...

Страница 3: ...the next unit It is the responsibility of the user to install cable and wire to the MULTICOMP MP002510 Modbus plug connector The connection diagram is shown below in Figure 1 Note that the connection...

Страница 4: ...for the GF U3000 V2 Ultrasonic Flowmeter The Modbus specification for RTU mode defines an 11 bit character frame containing an 8 bit character If Parity is used then only one stop bit is required If...

Страница 5: ...ssages The following message types are supported from the Modbus Application Protocol Specification Message Type Message Number Notes READ HOLDING REGISTERS 03 0x03 Read a contiguous block of register...

Страница 6: ...of the mantissa are stored in the higher address Some registers below contain bit mappings These values may be manipulated via the MASK WRITE REGISTER command 22 as outlined in Table 1 Bit fields are...

Страница 7: ...value Interface version uint16 0x5A00 R This is a check value and an interface version number This version is zero All values start at the base 0x5A00 2 1 Device ID uint16 GF U3000 V2 Ultrasonic Flow...

Страница 8: ...12 MBM to control digital output s on a unit 12 100 Reserved uint16 Sec 6 RZ 0 to 59 101 102 100 101 Date Time uint32 Min 6 R 0 to 59 Hour 5 0 to 23 Day 5 1 to 31 1st 1 Month 4 1 to 12 Jan 1 Year 6 b...

Страница 9: ...d 13 Reserved allocation of 13 LS bits of reg 133 Hot probe fault 1 Faulty or disconnected hot probe Cold probe fault 1 Faulty or disconnected cold probe Signal Loss 1 Device is online and has lost si...

Страница 10: ...Registers Registers highlighted as RW are updateable They provide the ability to update the unit s configuration Except for the Regime regis ter register 5 offset 4 all updateable registers can be up...

Страница 11: ...lags associated with them Values can be written into these registers but no action will be taken until the associated flag is activated There are three key flags that must be considered when updating...

Страница 12: ...uint16 year month day hour minute second Read the time and date starting at register offset 8 timeNdate Read2HoldingRegisters 8 Extract elements second timeNdate mod 2 6 timeNdate timeNdate div 2 6 m...

Страница 13: ...address 136 with the AND mask being set to 0xFFEF and the OR mask being 0x0010 This will start the update 5 Send a MASK WRITE REGISTER message command 22 or 0x16 to register address 5 with the AND mas...

Страница 14: ...entry for the moment Status Flags Online The unit is currently reading flow This flag is reset when the unit stops reading flow and enters the configuration mode Status Flags Urgent Error An urgent er...

Страница 15: ...15 GF U3000 V2 Ultrasonic Flowmeter Modbus Supplement to the operating instructions...

Страница 16: ...td Unit 2501 U Tower 120 Heungdeok Jungang ro Yeongdeok dong Giheung gu Yongin si Gyeonggi do Phone 82 31 8017 1450 Fax 82 31 217 1454 kor ps georgfischer com www gfps com kr Malaysia George Fischer M...

Отзывы: