background image

8

GF U3000 V2 Ultrasonic Flowmeter

Modbus Supplement to the operating instructions

8

7

Instru-
ment 
Status 
Flags

uint16

Online:1

R

Device is reading flow

Urgent Error:1

An urgent error has been reported

Remote Total Changes 
Disabled:1

Instrument has barred updates of all 
totals. 1=MBM changes disabled

Current Loop Alarm:1

1=active (current loop alarm active)

Digital Device 0 Alarm:1

1=active (Digital device 0 is currently 
unimplemented, so always 0)

Digital Device 1 Alarm:1

1=active (Digital Output 1)

Digital Device 2 Alarm:1

1=active (Digital Output 2)

Digital Device 3 Alarm:1

1=active (Digital Output 3)

Reserved:8

9,10

8,9

Date / 
Time

uint32

Sec:6

R

0 to 59

Min:6

0 to 59

Hour:5

0 to 23

Day:5

1 to 31; 1st = 1

Month:4

1 to 12; Jan = 1

Year:6 (base 2000)

Add 2000 for full year.

11

10

Reserved uint16

Reserved: 1
Outputs Available:3
Reserved:12

R

Not available at the time of writing, but 
may be used to allow Management 
system to control digital output(s)

12

11

Reserved uint16

Reserved:1

W

Not available at the time of writing but 
may be used to allow the

Output Values:3
Reserved:12

MBM to control digital output(s) on a 
unit

12-100

Reserved uint16

Sec:6

RZ

0 to 59

101, 
102

100-101

Date / 
Time 

uint32

Min:6

R

0 to 59

Hour:5

0 to 23

Day:5

1 to 31; 1st = 1

Month:4

1 to 12; Jan = 1

Year:6 (base 2000)

Add 2000 for full year.

103, 
104

102-103

Reserved uint16× 2

RZ

Reads Zero. Not used. Future Expansion

105, 
106

104,105

Measured 
Velocity

IEEE 754 SP

m/s, ft/s, ft/s, m/s

R

Metric1, Imperial, US Imperial, Metric2
Reads zero when not measuring flow.

107, 
108

106,107

Measured 
Flow

IEEE 754 SP

l/s, Imp gallon/s, US gallon/s, 
m3/hr

R

Metric1, Imperial, US

s, US gallon/s, m3/hr

Imperial, Metric2
Reads zero when not measuring flow.

109, 
110

108,109

Forward 
Total

IEEE 754 SP

litres, Imp gallons, US 
gallons,m3

RW

Metric1, Imperial, US Imperial, Metric2

111, 
112

110,111

Reverse 
Total

IEEE 754 SP

litres, Imp gallons, US 
gallons,m3

RW

Metric1, Imperial, US Imperial, Metric 2

113, 
114

112,113

Fwd 
Energy 
Total

IEEE 754 SP

kWH, BTU, BTU, kWH

RW

Metric1, Imperial, US Imperial, Metric2

115, 
116

114,115

Rev 
Energy 
Total

IEEE 754 SP

kWH, BTU, BTU, kWH

RW

Metric1, Imperial, US Imperial, Metric2

117-132 116-131

Reserved uint16× 16

RZ

Reads Zero. Not used. Future Expansi-
on.

133, 
134

132, 133

Instanta-
neous 
Power

IEEE 754 SP

kW, BTU/s, BTU/s, kW

R

Metric1, Imperial, US Imperial, Metric2
Reads zero when not measuring flow.

Содержание U3000 V2

Страница 1: ...er 2026161 F U3000 V2 Modbus Supplement MA_00138 EN 00 07 2022 Georg Fischer Piping Systems Ltd CH 8201 Schaffhausen Switzerland 41 52 631 30 26 info ps georgfischer com www gfps com 7 Units 4 Velocit...

Страница 2: ...dentification 13 3 9 Status Flags 14 4 GLOSSARY 14 Original instruction manual Disclaimer The technical data are not binding It does not constitute expressly warranted characteristics and neither guar...

Страница 3: ...the next unit It is the responsibility of the user to install cable and wire to the MULTICOMP MP002510 Modbus plug connector The connection diagram is shown below in Figure 1 Note that the connection...

Страница 4: ...for the GF U3000 V2 Ultrasonic Flowmeter The Modbus specification for RTU mode defines an 11 bit character frame containing an 8 bit character If Parity is used then only one stop bit is required If...

Страница 5: ...ssages The following message types are supported from the Modbus Application Protocol Specification Message Type Message Number Notes READ HOLDING REGISTERS 03 0x03 Read a contiguous block of register...

Страница 6: ...of the mantissa are stored in the higher address Some registers below contain bit mappings These values may be manipulated via the MASK WRITE REGISTER command 22 as outlined in Table 1 Bit fields are...

Страница 7: ...value Interface version uint16 0x5A00 R This is a check value and an interface version number This version is zero All values start at the base 0x5A00 2 1 Device ID uint16 GF U3000 V2 Ultrasonic Flow...

Страница 8: ...12 MBM to control digital output s on a unit 12 100 Reserved uint16 Sec 6 RZ 0 to 59 101 102 100 101 Date Time uint32 Min 6 R 0 to 59 Hour 5 0 to 23 Day 5 1 to 31 1st 1 Month 4 1 to 12 Jan 1 Year 6 b...

Страница 9: ...d 13 Reserved allocation of 13 LS bits of reg 133 Hot probe fault 1 Faulty or disconnected hot probe Cold probe fault 1 Faulty or disconnected cold probe Signal Loss 1 Device is online and has lost si...

Страница 10: ...Registers Registers highlighted as RW are updateable They provide the ability to update the unit s configuration Except for the Regime regis ter register 5 offset 4 all updateable registers can be up...

Страница 11: ...lags associated with them Values can be written into these registers but no action will be taken until the associated flag is activated There are three key flags that must be considered when updating...

Страница 12: ...uint16 year month day hour minute second Read the time and date starting at register offset 8 timeNdate Read2HoldingRegisters 8 Extract elements second timeNdate mod 2 6 timeNdate timeNdate div 2 6 m...

Страница 13: ...address 136 with the AND mask being set to 0xFFEF and the OR mask being 0x0010 This will start the update 5 Send a MASK WRITE REGISTER message command 22 or 0x16 to register address 5 with the AND mas...

Страница 14: ...entry for the moment Status Flags Online The unit is currently reading flow This flag is reset when the unit stops reading flow and enters the configuration mode Status Flags Urgent Error An urgent er...

Страница 15: ...15 GF U3000 V2 Ultrasonic Flowmeter Modbus Supplement to the operating instructions...

Страница 16: ...td Unit 2501 U Tower 120 Heungdeok Jungang ro Yeongdeok dong Giheung gu Yongin si Gyeonggi do Phone 82 31 8017 1450 Fax 82 31 217 1454 kor ps georgfischer com www gfps com kr Malaysia George Fischer M...

Отзывы: