6

Signet 0250 Setup Tool

Windows PC

USB

GND

Data

+5V out

Signet 2250

Hydrostatic

Level Sensor

GND

Data

+5V

Signet 2250 Hydrostatic Level Sensor Setup

2250 Wiring

2250 Operation

1.  Select the engineering units for the application: inches, 

feet, centimeters or meters.

2.  Set the Level measurement where the Loop output must 

equal 4 mA.

3.  Set the Level measurement where the Loop output must 

equal 20 mA.

•  Minimum setting for both endpoints is 0.
•  Maximum setting for both endpoints is based on the 

maximum pressure rating of the sensor. 

•  Maximum setting, -XU sensor (0-10 psi)
•  7.03 m = 703.1 cm = 23.07 ft. = 276.8 in.
•  Maximum setting, -XL sensor (0-50 psi)
•  35.15 m = 3515.0 cm = 115.33 ft. = 1384.0 in.

4.  Click "Write" to copy settings from the display into the 

Magmeter.

 

Click "Save" to save the settings from the display to a 
computer fi le.

5.  To use a saved fi le:

• Click "Load"
•  Navigate to the saved fi le
• Select Open
• Click "Write"
•  Click "Read" to confi rm

Signet 2350 Temperature Sensor Setup

Windows PC

Signet 2350

Temperature

Sensor

USB

GND

Data

+5V out

GND

Data

+5V

2350 Wiring

2350 Operation

1.  Select the engineering units for the application:
 

°C (Celsius) or °F (Fahrenheit).

2.  Set the Temperature measurement where the Loop output 

must equal 4 mA.
•  Minimum setting -10 °C (14 °F)
•  Maximum setting 100 °C (212 °F)

3.  Set the Temperature measurement where the Loop output 

must equal 20 mA.

•  Minimum setting -10 °C (14 °F)
•  Maximum setting 100 °C (212 °F)

4.  Click "Write" to copy the settings from the display into the 

Magmeter.

 

OR

 

Press "Save" to save the settings from the display to a 
computer fi le.

To use a saved fi le:

• Click "Load"
•  Navigate to the saved fi le
• Select Open
• Click "Write"
•  Click "Read" to confi rm.

Содержание Signet 3-0250

Страница 1: ...100 C 4 to 212 F Relative Humidity 0 to 90 non condensing Operating Temperature 15 to 55 C 5 to 131 F module only 3 To run the program from the CD Right click the START button and select EXPLORE Navig...

Страница 2: ...setup capability of the 0250 is more complex with the magmeters than with other sensors Read these instructions carefully before attempting to modify a Magmeter CAUTION Do not connect power directly...

Страница 3: ...s Set the time the Magmeter will use as the averaging period Example With averaging at 14 seconds each display is an average of the previous 14 seconds input Use higher averaging times to smooth the d...

Страница 4: ...exit the program If the settings will be used again click SAVE Name the file and save it on the computer hard drive Read Read and display the existing settings from the Magmeter Write Write from the d...

Страница 5: ...atic The best solution to these problems is to correct any piping deficiency that causes the instability This may involve longer straight runs upstream reducing the pipe size to maintain a full pipe a...

Страница 6: ...lay into the Magmeter Click Save to save the settings from the display to a computer file 5 To use a saved file Click Load Navigate to the saved file Select Open Click Write Click Read to confirm Sign...

Страница 7: ...to the saved file Select Open Click Write Click Read to confirm Signet 2750 pH Sensor Setup 2750 Wiring 2750 Operation 1 Select the engineering units for the application pH or ORP 2 Set the pH or ORP...

Страница 8: ...0 seconds the 0250 will record the temperature once every minute The 0250 saves data files in csv format The maximum number of records allowed for this type of file is 65535 If the logging interval is...

Отзывы: