6
Signet 0250 Setup Tool
Windows PC
USB
GND
Data
+5V out
Signet 2250
Hydrostatic
Level Sensor
GND
Data
+5V
Signet 2250 Hydrostatic Level Sensor Setup
2250 Wiring
2250 Operation
1. Select the engineering units for the application: inches,
feet, centimeters or meters.
2. Set the Level measurement where the Loop output must
equal 4 mA.
3. Set the Level measurement where the Loop output must
equal 20 mA.
• Minimum setting for both endpoints is 0.
• Maximum setting for both endpoints is based on the
maximum pressure rating of the sensor.
• Maximum setting, -XU sensor (0-10 psi)
• 7.03 m = 703.1 cm = 23.07 ft. = 276.8 in.
• Maximum setting, -XL sensor (0-50 psi)
• 35.15 m = 3515.0 cm = 115.33 ft. = 1384.0 in.
4. Click "Write" to copy settings from the display into the
Magmeter.
Click "Save" to save the settings from the display to a
computer fi le.
5. To use a saved fi le:
• Click "Load"
• Navigate to the saved fi le
• Select Open
• Click "Write"
• Click "Read" to confi rm
Signet 2350 Temperature Sensor Setup
Windows PC
Signet 2350
Temperature
Sensor
USB
GND
Data
+5V out
GND
Data
+5V
2350 Wiring
2350 Operation
1. Select the engineering units for the application:
°C (Celsius) or °F (Fahrenheit).
2. Set the Temperature measurement where the Loop output
must equal 4 mA.
• Minimum setting -10 °C (14 °F)
• Maximum setting 100 °C (212 °F)
3. Set the Temperature measurement where the Loop output
must equal 20 mA.
• Minimum setting -10 °C (14 °F)
• Maximum setting 100 °C (212 °F)
4. Click "Write" to copy the settings from the display into the
Magmeter.
OR
Press "Save" to save the settings from the display to a
computer fi le.
To use a saved fi le:
• Click "Load"
• Navigate to the saved fi le
• Select Open
• Click "Write"
• Click "Read" to confi rm.