10
2.7 Analog Output Connections
0 to 20/4 to 20 mA isolated or non-isolated
output as well as 0 to 5/0 to 10 VDC isolated or
non-isolated outputs are available. See section
4.4 for a list of available output cards.
Chapter 3
System
Configuration
3.1 Introduction
All the functions which can be modified are
contained in three menus:
The CAL (calibrate) menu contains those functions
which pertain to the input signal and how it is
interpreted by the instrument (i.e. K-factor, totalizer
reset). The CAL menu also provides access to the
security code and display contrast features.
The RELAY menu contains all the functions neces-
sary to control any output relays, such as relay
Note:
The maximum loop impedance for the 4 to 20 mA/0 to 20 mA output is 425
Ω
.
The minimum load impedance for the 0 to 5 V/0 to 10 V output is 1 k
Ω
(1000
Ω
). To
reduce the possibility of noise interference, separate output lines from AC power/relay lines.
Figure 7
Analog output wiring
*The 4 to 20 mA
option is jumper
configurable for
0 to 20 mA
operation. Refer to
section 4.6
SS CNT GND PLS
R+ R-
Tx GND Rx
A+ A-
BLK RED SHLD
OUTPUT
ANL2
SERIAL
A in
SENSOR
Analog Ouput #2
(i.e. 0 to 5 VDC)
etc.
-
+
L
1
AC IN
+ GND NO C NC
RLY1
DC IN
NO C NC
RLY2
ANL1
-
Analog Output #1
(i.e. 4 to 20 mA*)
etc.
+
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8
R+ R-
N