9
2.3
Installation
Remove the blanking plug on the rear side of the positioner.
Screw the M12x1.5 wiring gland into the positioner.
Place the feedback module in the plug-in position (EXTENSION) as shown and push it in.
If the feedback module is pushed in incorrectly, damage may occur to the
module and the positioner.
Connect the feedback module as shown in the wiring diagram below.
The feedback signal does not require calibration.
CH1
6
RM-2
+
-
24V DC
+
-
4-20 mA
5 4 3 2 1
CH2
Terminal 1:
Feedback signal, positive pole
Terminal 2:
Feedback signal, negative pole
Terminal 3:
Upper limit value sender output
Terminal 4:
Upper limit value sender input
Terminal 5:
Lower limit value sender output
Terminal 6:
Lower limit value sender input