background image

6

Signet 9900 Modbus Module

Status Register
Registers 40001 – 40002
Register.Bit

Description

40001.0

Sensor reading is Good, no errors

40001.1

Wrong Sensor Connected

40001.2

Check Sensor

40001.3

Missing Sensor

40001.4

Sensor Error

40001.5

Secondary Reading is Totalizer

40001.6

Secondary Reading not Available

40001.7

Reset to Default Jumper Active

40001.8

9900 Communication Active 

40001.9

Manufacturing Area Protected

40001.10

Device using Default Communication Parameters

40001.11 – 40002.15

Not Used

 

Readings / Sensors
Instrument Type

Measurement  Type 
Reg 40007

Primary
Reg 40003

Secondary
Reg 40005

Factory 

1

0x0000

NA

NA

Flow 

0x4201

Flow

Totalizer 

2

pH 

0x5102

pH

Temperature

ORP

0x5103

ORP

Raw mV

Cond/Res

0x5704

Cond/Res

Temperature

Pressure

0x4105

Pressure

NA

Level/Volume

0x5C06

Level

Volume

Temperature

0x4007

Temperature

NA

4 to 20 mA Input

0x0008

Scaled Input

Raw mA

Salinity

0x5A09

Salinity

Temperature

Dissolved Oxygen

0x510B

Dissolved Oxygen

Temperature

Batch

No Modbus Operation in Batch Mode

1.  Factory and Batch Instrument types do not update the Primary or Secondary readings.
2.  Secondary readings for fl ow are only available in 9900 Generation 4 or greater transmitters.

In Generation 4 transmitters the user can set the secondary reading to be either the permanent 
or resettable Totalizer.

Programming Map

Format (Byte Orders)
Floats
Register

Data

Bytes

IEEE754 Float 0x570A4318
Result 152.34

49006

0

Big Endian

40003

0x570A

C D

40004

0x4318

A B

49006

1

Little Endian

40003

0x4318

A B

40004

0x570A

C D

Содержание 3-9900.270-MX

Страница 1: ...efore or after the base unit is mounted If the 9900 Base Unit will be mounted using the accessory wall mount kit 3 9900 392 install plug in modules rst If the Direct Conductivity Resistivity Module or...

Страница 2: ...y Information Product Registration Safety Information CAUTION Exercise care when installing module Do not bend connecting pins Align pins and connectors then push module firmly into place Avoid Electr...

Страница 3: ...White Gray D0 RS485 Pin 2 D1 RS485 Pin 1 V 12 to 24 VDC Pin 3 V 12 to 24 VDC Common Pin 4 Com Reset GND Pin 5 Brown D0 RS485 Yellow D1 RS485 Black V 12 to 24 VDC White V 12 to 24 VDC Common Gray Com...

Страница 4: ...te Data Type Description 49104 1 Read UINT 9900 HSB Transactions 49105 1 Read UINT Second Counter 49106 1 Read UINT Bus Message Counter 49107 1 Read UINT Bus Message Error Counter 49108 1 Read UINT Sl...

Страница 5: ...gister 49005 0 No Parity 1 Odd Parity 2 Even Parity Default 2 Set baud Rate Register 49004 0 1200 1 2400 2 4800 3 9600 4 19200 5 38400 6 57600 7 115200 Default 4 Write Modbus Address to Register 49007...

Страница 6: ...5102 pH Temperature ORP 0x5103 ORP Raw mV Cond Res 0x5704 Cond Res Temperature Pressure 0x4105 Pressure NA Level Volume 0x5C06 Level Volume Temperature 0x4007 Temperature NA 4 to 20 mA Input 0x0008 Sc...

Страница 7: ...e BPH 134 242 Barrels per Hour BPD 135 Barrels per Day FT S 20 Feet per Second M S 21 Meters per Second All Others 252 All other ow units Flow Totalization Secondary All Units 240 pH Primary pH 59 pH...

Страница 8: ...ssembly for M2 3 9900 270 CB3 159 200 125 Replacement M12 Connector Assembly for M3 3 9900 270 CB4 159 200 129 Replacement Cable Assembly for M4 5541 5005 159 855 021 5 meter 16 ft M12 cable 5541 5010...

Отзывы: