Product description

This free-swing door closer is approved for installation 
on single leaf fire and smoke protection doors.  
The system contains an electrically actuated free-
swing device which is controlled by an integrated 
smoke switch control unit. The system is triggered if 
there is a fire or a power failure, and the door closes 
automatically

Further documents

The components supplied by GEZE include further 
documents describing the installation or connection 
of the system. These must be read and followed.

 

à

Door closer installation instructions

 

à

Door closer user information

 

à

Instructions for installation, commissioning, ope-
ration and after-sales service maintenance of FA 
GC (available at www.geze.com). 

Safety notices

Follow the document “Instructions for the installati-
on, commissioning, operation and after-sales service 
maintenance of GEZE hold-open system FA GC” for 
electrical connection and commissioning (available at 
www.geze.com).

DANGER! 

Danger of electric shock!

Electric wiring must only be carried out by professio-
nal electricians.

 

X

Interrupt power supply! Secure against reactivation.

 

X

A 16 A circuit breaker must be provided on site 
(suitable for the electrical installations). 

 

X

Use cable protection for the 230 V cable when 
leadingthrough plaster.

 

X

Insert the cable protruding from the wall through 
therespective openings of the smoke switch 
housing only.

Technical data 

Protection rating

II

 

 

IP rating

IP 20; only for dry rooms

Ambient temperature

-5 °C bis 50 °C

230 V supply cable

NYM-J, 3 x 1,5 mm

2

Supply voltage: 

230 V AC +10 % / –15 %, 

Operating voltage: 

24 V DC ± 15%

maximum current con-
sumption

260 mA

Installation 

Check the door for ease of movement before star-

ting work. 

Installation details 

The remarks are intended as work instructions as well 
as the associated graphical installation instructions.

to

 

1

 

X

Drill fixing holes for door closer, guide rail, smoke 
switch housing (A) and optionally additional 
connections (B).

to

 

8

DANGER! 

Follow safety precautions

CAUTION!

When clipping on the cover panels do not squeeze 
the cables. Fit the protective cap so that the smoke 
switch opening is concealed in the cover panel in 
order to protect the interior of the system from con-
tamination before commissioning.

Initial operation 

CAUTION! 

The installation of the smoke switch may only take 
place shortly before commissioning. If installed 
early, there is a danger of contaminating the smoke 
switch with construction dust. This can considerably 
shorten the life span of the smoke switch.

to 

c

 

X

The protective cap must be removed when the 
hold-open system is commissioned.

Initial switch-on, test

 

X

Remove the protective cap (if not already done).

 

X

Turn power on.  
Status display light is GREEN.

 

X

First open the door through > 90° against the 
closing force. This tensions the door selector and 
holds it in place electro-hydraulically. After this 
each time the door is operated the comfort latch 
is overridden and the closing function is not acti-
vated, i.e. the door can be moved freely. 

 

X

Press the reset button on the smoke switch. 
The status display turns YELLOW for approximately 
4 seconds. The door closes. The status display then 
again turns GREEN.

Acceptance test

An acceptance test must be carried out in order to 
ascertainthe correct function and installation accor-
ding to the regulation, once the installation has been 
completed. For this, follow the document “Instruc-
tions for the installation, commissioning, operation 
and after-sales service maintenance of GEZE hold-
open system FA GC”.

Maintenance, care, repair

Regular servicing has to be carried out. For more infor-
mation on this, please observe the document “Instruc-
tions for Installation, Commissioning, Operation and 
Maintenance of the GEZE Hold-Open Device FA GC”.

Содержание TS 5000 RFS KB

Страница 1: ...TS 5000 RFS 3 6 KB DE EN FR ES 156107 00 ...

Страница 2: ...TS 5000 RFS 3 6 KB 2 DE Deutsch 3 EN English 4 FR Français 5 ES Español 6 TS 5000 RFS 3 6 KB 7 ...

Страница 3: ...ösetasters bei Freilaufschließern in Deutschland zwingend vorgeschrieben Montagehinweise Die Hinweise verstehen sich ergänzend zu den Arbeits schritten der zugehörigen grafischen Montageanlei tung zu 1 X Befestigungslöcher für Schließer Gleitschiene Stromzuführung 230 V A und optional für Zu satzanschlüsse B bohren zu 8 GEFAHR Sicherheitshinweise beachten VORSICHT Bei aufklispsen der Blenden Kabel...

Страница 4: ...k instructions as well as the associated graphical installation instructions to 1 X Drill fixing holes for door closer guide rail smoke switch housing A and optionally additional connections B to 8 DANGER Follow safety precautions CAUTION When clipping on the cover panels do not squeeze the cables Fit the protective cap so that the smoke switch opening is concealed in the cover panel in order to p...

Страница 5: ...de montage graphique correspondant pour 1 X Percer des trous de fixation pour le ferme porte la glissière le boîtier du détecteur de fumée A et en option pour des raccords supplémentaires B pour 8 DANGER Respecter les consignes de sécurité PRUDENCE En déclipsant le cache veillez à ne pas coincer le câble Placer le couvercle de protection de façon à couvrir l ouverture du détecteur de fumée dans le...

Страница 6: ...lementan los pasos de traba jo de las instrucciones gráficas de instrucciones de instalación de 1 X Taladrar los orificios de fijación para el cierrapuer tas la guía deslizante la carcasa de la central de detección de humos A y de forma opciona pa ra las conexiones auxiliares B de 8 PELIGRO Observe las indicaciones de seguridad CUIDADO Al cerrar el clip de los paneles no aprisionar el cable Coloqu...

Страница 7: ...7 10 mm 2 2x 5 20 4x 5 60 4x M5 55 2x M5 16 3 mm 4 mm 5 mm ...

Страница 8: ... 2 135 0 2 38 120 428 5 0 2 1 44 590 37 26 16 Ø 10 130 1 120 428 5 0 2 160 0 2 1 135 0 2 38 44 590 26 37 16 Ø 10 A A 1 2 B B 4x M5 20 4x 5 35 4x M5 50 142 120 428 5 0 2 160 1 142 1 160 0 2 65 16 590 26 37 16 Ø 10 A B A B A Ø 16mm B Ø 16mm A Ø 16mm B Ø 16mm ...

Страница 9: ...9 2 4 mm 14 Nm 3 3 5 mm click click 4 5 2 2 3 Nm 1 L R ...

Страница 10: ...10 4 M5 20 5 35 M5 50 5 M5 55 5 60 230 V AC ...

Страница 11: ...11 7 6 2x M5 16 2x 5 20 1 1 2 2 ...

Страница 12: ...12 9 5 mm 8 2 L1 N PE 3 EN 1154 1400 1250 1150 950 6 5 4 3 5 4 3 a mm EN 6 230 V AC 1 4 2 ...

Страница 13: ...13 10 1 2 Nm 90 7s 11 2 1 3 4 5 click click ...

Страница 14: ...14 a 2 1 2 b 4 1 2 3 3 4 ...

Страница 15: ...15 c 5 mm 12 11 10 5 2 4 GEZE 1 90 GEZE 2 45 6 45 3 ...

Страница 16: ...Ltd Branch Office Beijing E Mail chinasales geze com cn www geze com cn France GEZE France S A R L E Mail france fr geze com www geze fr Hungary GEZE Hungary Kft E Mail office hungary geze com www geze hu Iberia GEZE Iberia S R L E Mail info geze es www geze es India GEZE India Private Ltd E Mail office india geze com www geze in Italy GEZE Italia S r l E Mail italia it geze com www geze it GEZE E...

Отзывы: