IQ lock AUT, EL / EL DL, EM / EM DL, C / C DL, M / M DL
59
What if?
Alarm/fault
Cause
Consequence
Remedial action
No signal from the Reed
contact
Sensing distance of the Reed
contact exceeded or power
supply cable for the Reed contact
defective
– or –
Input external door contact
on the control defective
Electrical timeout
function still working.
Door locks during
door closing process or
remains locked when
door is closed.
Door mode “door closed” is
not signalled.
X
Check Reed contact, sensing
distance observed?
X
Check continuity, check input
of external door contact on the
control.
Lock no longer locks
Power supply cable defective
Bolt no longer extends
X
Replace power supply cable.
Door leaf cannot close
Cross latches hit the strike plate
hard
Door leaf cannot close,
latches grind at the strike
plate
X
Lubricate the cross latches
lightly with a lubricant
approved by GEZE.
Auxiliary latch can no longer be
actuated
X
Mobilise the auxiliary catch
carefully.
Lever lock IQ lock EM / IQ lock EM DL
Alarm/fault
Cause
Consequence
Remedial action
Manual unlocking via the
outer door handle not
possible
Magnet is not energised
Outside handle is not
engaged and is disabled
X
Check the polarity of the 24
V DC input and replace if
necessary.
– and/or –
X
Check the continuity of the
power supply cable.
If the power supply cable and
polarity are both OK:
X
Replace the lock.
The door can be pushed or
pulled open by hand
Cross latch cannot be
positioned
– or –
Lock cylinder is jammed
Bolt blocked in retracted state
X
Position the strike plate
correctly.
– or –
X
Check actuation of the
nightlatch function using the
key.
Door handle is jammed in
actuated position
– or –
Handle return spring is
broken
The door handle does not
return to its initial position
after actuation and there is
no locking signal given
X
Loosen the screws, lubricate the
handle guide, correct fastening.
– or –
X
Replace the lock.
Auxiliary latch is not actuated Lock does not lock when the
door is closed
X
Check the clearance of the door
leaf.
Bolt shoots out again
immediately after the door
has been opened
Door handle has not been
pressed down completely.
– or –
Auxiliary latch is jammed
Slider is not held in
permanently unlocked
position, door cannot close
and be locked properly
X
Press the door handle as far as
it will go.
X
Check the tension-free fit of the
lock.
Rework the lock recess if necessary.
If there is no change in lock
behaviour:
X
Replace the lock.
The auxiliary latch closes with
door closed with “Off”
Strike plate has been
reworked and hollowed out
too much
–
X
Open the door and replace the
strike plate.
Door leaf cannot close
Cross latches hit the strike
plate hard
Door leaf cannot close, latches
grind at the strike plate
X
Lubricate the cross latches
lightly with a lubricant
approved by GEZE.
Auxiliary latch can no longer
be actuated
–
X
Mobilise the auxiliary catch
carefully.
Contacts are not signalling
Fittings set installed twisted
– or –
Lockcase fitted in the recess
under mechanical tension
Contacts in the lock are not
actuated by the integrated
slider
X
Remove the fittings set.
X
Check the tension-free fit of the
lock.
X
Rework the lock recess if
necessary, mobilise the lock or
replace the lock.
Power supply cable is
defective
Relaying of contacts not
possible
X
Check power supply cable
through or replace lock.
Содержание IQ lock AUT
Страница 56: ...IQ lock AUT EL EL DL EM EM DL C C DL M M DL 56 Wiring diagrams ...
Страница 66: ...IQ lock AUT EL EL DL EM EM DL C C DL M M DL 66 Annex ...
Страница 68: ...IQ lock AUT EL EL DL EM EM DL C C DL M M DL 68 Annex ...
Страница 70: ...IQ lock AUT EL EL DL EM EM DL C C DL M M DL 70 Annex ...
Страница 71: ...IQ lock AUT EL EL DL EM EM DL C C DL M M DL 71 Annex ...