IQ lock AUT, EL / EL DL, EM / EM DL, C / C DL, M / M DL
38
Wiring diagrams
6.12 IQ lock EL with smoke switch control unit FA GC 150/160
X
Follow the mechanical installation instructions for IQ lock.
X
Heed the wiring diagram for the hold-open system FA CG 150.
X
Set jumper J3 on the smoke switch control unit (RSZ6) to 2/3.
X
Separate the breaking point in the first relay base.
X
Do
not
separate the breaking point in the last relay base.
X
Set jumper J1 on the MST 210 to 2/3.
X
Press the reset button for commissioning.
X
After activating the smoke switch control unit or the smoke switches, press the reset push button.