Setting parameters
6.10 Parameters and setting ranges
6.10.1 Drives
Parameter
Parameter values for the drive
Menu level 2
Menu level 3
Slimchain
Powerchain
E 250 NT
F 1200+
Stroke
Ventilate [mm]
Min.
10
default
300
Spindle length
180
Max.
Alarm stroke value
180
Alarm [mm]
Min.
Ventilation stroke value
-
default
Chain length
Spindle length
-
Max.
Chain length
Spindle length
-
Reversing [mm]
Min.
0
0
default
15
25
Max.
50
25
Relief [0.1mm]
Min.
0
-
default
5
-
Max.
10
-
Speed
Open [mm/s]
Min.
2
11
default
5
11
Max.
7
32
Close [mm/s]
Min.
2
11
default
5
11
Max.
16
32
Alarm [mm/s]
Min.
7
-
default
dependent on alarm stroke
-
Max.
–
16
10 (stroke 500)
otherwise 7
-
Turn ventilation
[mm/s
2
]
Min.
-
16
default
-
80
Max.
-
80
Automatic ventila-
tion [mm/s
2
]
Min.
-
11
default
-
11
Max.
-
32
Acceleration
Open [mm/s]
Min.
1
-
default
5
-
Max.
20
-
Close [mm/s]
Min.
1
-
default
5
-
Max.
20
-
Alarm
[mm/s
2
]
default
10
-
Braking
Open ventilation
[mm/s
2
]
Min.
5
-
default
10
-
Max.
20
-
Close ventilation
[mm/s
2
]
Min.
1
-
default
1
-
Max.
10
-
Alarm [mm/s
2
]
default
10
-
Closing system
force
[%]
Min.
50
-
default
70
-
Max.
100
-
Switch interface
[0] Self-retain
[1] Dead man
Min.
Dead man
default
Self-retain
Max.
Self-retain
Stop conditions
[0] same key
[1] other key
[2] any key
Min.
same key
default
any key
Max.
any key