Setting parameters
6.1 Speed ventilation opening/alarm opening/turn opening/automatic opening/
closing
The value range for the speeds is limited at the service terminal ST 220. High speeds lead to higher wear.
The "alarm opening speed" parameters cannot be set. Here, the current speed which is calculated from the current
alarm stroke is displayed.
6.2 Ventilation/alarm/relief/reversing stroke
Ventilation stroke
The value range for ventilation stroke and alarm stroke parameters can be set using the service terminal ST 220.
The alarm stroke cannot be smaller than the ventilation stroke. The software restricts the max. ventilation stroke
to the alarm stroke set.
Relief stroke
The relief stroke defines the extent to which the load on the drive is relieved after the closing position has been
reached.
Reversing stroke
The reversing stroke defines the extent to which the drive is reversed if the window is obstructed before the
open or closing position is reached.
6.3 Ventilation braking/ventilation acceleration
Ventilation braking
à
The "ventilation braking", “open brakes” parameters describes the brake ramp during opening and reversing.
à
The "ventilation braking", “close brakes” parameters describes the brake ramp during closing and reversing.
Ventilation acceleration
à
The "ventilation expedite", “open exp” parameters describes the expediting ramp during opening and reversing.
à
The "ventilation expedite", “close exp” parameters describes the expediting ramp during closing and reversing.
Possible damage to the window!
High expediting values lead to high start-up current.
X
Only change the settings following consultation with GEZE.
6.4 Closing position force
This parameter describes the closing force during finding of the closing position.
The teaching run always occurs at max. force. The force to reach the overload cut-off remains unaffected by this.
The closing force influences the airtightness and life span of the windows and fitting parts.
The setting may only be made by specialist authorised personnel.
6.5 Mode of operation push button
à
The key interface (IQ gear) is connected.
à
For the key interface (IQ gear) to be able to be used, the polarity must be set to "close".
In the mode of operation push button, a distinction is made between the following operating modes:
à
Self-locking;
In the self-locking mode of operation, the window continues to open after the push button has been pressed,
even if the key is released again.
The movement only stops when the end position (ventilation stroke parameters set) has been reached. During
closing, the window moves to the closed position.
To stop the movement in an intermediate position, the stop condition must be defined (see Section 6.6).
à
Dead-man;
In the dead-man mode of operation the window opens or closes as long as the respective push button is kept
pressed.
The operating mode push buttons are set as described in Section 6.6.