Set parameters of the IQ box KNX functions using the ETS

Use the ETS software to set parameters of the IQ box KNX.

7.1  Description of the functions

ETS parameters 

menu item

Function

Description

General informa-

tion

Energy-saving mode

After an adjustable waiting period, the IQ box KNX enters 

energy-saving mode. The drives are switched to energy-saving 

mode and are only re-activated with the next movement com-

mand.   

General informa-

tion

Reaction to a  

bus power failure

Behaviour of the drives if the KNX bus power fails

General informa-

tion

Reaction after  

restoration of power

Behaviour of the drives after restoration of power

General informa-

tion

Status delay after restoration 

of power

In order to reduce the bus load after restoration of power, a 

status transmission delay can be set here 

Operation

Manual controls

There are several possibilities for the manual controls via KNX:

 

à

Addressing the movement command Open/Close (KNX 

Com. Object # 1)

 

à

Addressing the movement command Open/Close (KNX 

Com. Object # 1) and Stop (KNX Kom. Object # 2) long-

term and short-term function for blinds operation

 

à

Addressing the movement command target position by 

stating percentage (KNX Com. Object # 3)

Operation

Speed  

Manual controls

Open/Close speed as a percentage of the max. ventilation 

speed of the drive in manual mode (actual max. ventilation 

speed depending on load).  

To secure windows against jamming, a leaf speed of < 5 

mm/s can be required within the framework of a safety 

analysis.

 Drive noise increases as speeds increase.

Operation

Interval ventilation

Settable step width in %, by which the window is moved when 

opening or closing when pressing the button. Additional 

pushes of the button are accumulated. Interval ventilation can 

be controlled using the blinds function like the normal manual 

controls. Open/Close over long-term operation and Step/Stop 

over short-term operation.

Operation

Gap ventilation

When triggering the gap ventilation function, the window

is opened to a settable window position in %.

Operation

Timed ventilation

When the timed ventilation function is triggered, the window 

is opened to a window position settable in % and automati-

cally closes again after the end of a settable ventilation period. 

Operation 

Block window

2 block objects, with which the window is closed in manual 

mode. Unblocking takes place via the block object.

E.g. for sequence controls with sun protection, blocking the 

window if heating or air-conditioning is switched on.  

Automatic

Automatic mode

For automatic control of the windows, e.g. via a central KNX 

room/building control unit with defined speed. Lower priority 

as manual mode

Automatic

Speed automatic

Open/Close speed as percentage of the max. ventilation speed 

of the drive in automatic mode. (actual max. ventilation speed 

depending on load)

To secure windows against jamming, a leaf speed of < 5 

mm/s can be required within the framework of a safety 

analysis.

 Drive noise increases as speeds increase.

Содержание IQ box KNX

Страница 1: ...IQ box KNX 166560 00 EN Commissioning manual Prog Ru n...

Страница 2: ...diagram 6 5 Test operation and commissioning of the IQ windowdrives 7 5 1 Test operation 7 5 2 KNX commissioning 7 5 2 1 Load ETS product database IQ box KNX 7 5 2 2 Assign physical address of the IQ...

Страница 3: ...is enclosed with the IQ box KNX and contains the most important product information and instruc tions about the electrical connection and about commissioning of the IQ box KNX IQ windowdrives install...

Страница 4: ...k Ensure that the connection to the power supply is only carried out by a qualified electrician The power con nection and safety earth conductor test must be carried out in accordance DIN VDE 0100 610...

Страница 5: ...4 V external 3 2 2 IQ box KNX top hat rail fitting to top hat rail IQ box KNX top hat rail Power supply NT 1 5 4 2 A 24 V HS GEZE surface housing ID 152010 with 35 mm top hat rail for 6 modules Prog R...

Страница 6: ...mounting wiring diagram 8 9 10 11 12 A B S L GND 24V 33 32 COM A S LIN B S L L A B S A B 230V AC Fenster window 4 24 V DC max 6 A 3 5 7 6 IQ box KNX KNX KNX KNX 1 1 2 4 2 IQ box KNX top hat rail wirin...

Страница 7: ...first time the closing position of the window is detected during the first closing procedure and is saved automatically Should the drive reverse after reaching the closing position drive opens by app...

Страница 8: ...ndow Closed State 1 002 C T 1 Bit OUT T 15 Window Not closed State 1 002 C T 1 Bit OUT T 16 Window Do open State 1 002 C T 1 Bit OUT T 17 Window Do close State 1 002 C T 1 Bit OUT T Alarm 21 Alert Saf...

Страница 9: ...cure windows against jamming a leaf speed of 5 mm s can be required within the framework of a safety analysis Drive noise increases as speeds increase Operation Interval ventilation Settable step widt...

Страница 10: ...lation speed Not suitable for RWA Alarm Wind alarm Rain alarm For wind alarm a binary wind alarm and a wind alarm as threshold value in m s can be selected After the end of the wind rain alarm and a s...

Страница 11: ...time 1 second 5 seconds 10 seconds 30 seconds 1 minute 2 minutes 5 minutes 10 minutes 20 minutes 30 minutes Open window Off time 1 second 5 seconds 10 seconds 30 seconds 1 minute 2 minutes 5 minutes...

Страница 12: ...ventilation Disabled Enabled Window position 0 100 50 4 Window Gap ventilation Trigger Time ventilation Disabled Enabled Window position 0 100 50 5 Window Time ventilation Trigger Ventilation time 5 1...

Страница 13: ...omatic Lock Switch Locked to close Unlock Via object 9 Automatic Lock Switch Until timeout Locking time min 1 300 30 9 Automatic Lock Switch Locked to open and close Unlock Via object 9 Automatic Lock...

Страница 14: ...d state Disabled On change 12 13 14 15 16 17 Window Position between State Window Opened State Window Closed State Window Not closed State Window Do open State Window Do close State Cyclic Cycle time...

Страница 15: ...action on safety alert Close window Open window Type wind alert Binary 23 Alert Wind alert Switch Threshold Threshold windspeed m s 2 30 4 22 Alert Wind speed value m s Behavior after wind rain alert...

Страница 16: ...without self locking Close 32 Button 1 Cl 33 Drive com mand Step Stop Position Window position 0 100 50 33 Button 1 Cl 33 Position Value Button 2 Cl 32 Disabled Lokal Drive type Tip op eration with se...

Страница 17: ...ion Disabled On change 41 Service Check unit State Error information Disabled Error unit Send condition On change 42 Service Error unit State Cyclic Cycle time min 1 255 50 Error collection Send condi...

Страница 18: ...n group Local push button Expanded function examples KNX Easy ventilation controls All basic functions can be realised through the grouping of several windows centrally for the entire ventilation grou...

Страница 19: ...tion examples KNX Automatic closing when the air conditioning is activated If the air conditioning is activated the windows are closed automatically Blocking of the manual opening As long as the air c...

Страница 20: ...idity are exceeded intelligent ventilation is ap plied until the air quality returns to the requirements Controls depending on times of day and usage Ventilation at certain times depending on room us...

Страница 21: ...ox KNX Check length of the connection cable to the drive The overall cable length between IQ box KNX and window must not exceed max 15 m Check software version of the drives on the identification plat...

Страница 22: ...GEZE IQ Box KNX 22...

Страница 23: ...GEZE IQ Box KNX 23...

Страница 24: ...om cn France GEZE France S A R L E Mail france fr geze com www geze fr Hungary GEZE Hungary Kft E Mail office hungary geze com www geze hu Iberia GEZE Iberia S R L E Mail info geze es www geze es Indi...

Отзывы: