GEZE IQ box KNX Скачать руководство пользователя страница 7

GEZE IQ Box KNX

7

 

1  Optional further Slave drives (with Syncro) or locking drives 
2  Additional branch box for the connection of several drives 
3  Power supply 24V DC  

IQ windowdrive 

Input S33 (window CLOSED); parameters can be set  

Input S32 (window OPEN); parameters can be set   

e.g. Vent switch LTA-24-AZ 

Window OPEN key  

Window CLOSED key 

10  Status LED (green)   

Continuous light 
Slow flashing 
Fast flashing 

Function OK  
No communication with drive   
supply voltage polarity reversed 

11  KNX programming LED (red) for commissioning KNX-BUS 
12  KNX programming key for commissioning KNX-BUS 
*) 

In the case of 24 V DC and a longer power supply line, the cable must have a sufficiently large cross-section in order to 

prevent a voltage drop. Calculate the cross-section.

The overall cable length between IQ box KNX and window must not exceed max. 15 m. 
With Synchro or locking drives, all the individual drive cables count.

 

 

Note the wiring diagram for IQ windowdrives ID 148327.  

Can only be used with GEZE IQ windowdrives from software version 3.0 onwards. 

Test operation and commissioning of the IQ windowdrives

5.1  Test operation

Following connection of the drives and the 24 V supply voltage, the key “Window OPEN” (9) and the key “Window 
CLOSED” (8) (see fig. IQ box KNX top hat rail + flush mounting) can be use to carry out a test run, even if the KNX 
system has not been programmed at this point. 
 If the IQ windowdrives are being operated for the first time, the closing position of the window is detected 
during the first closing procedure and is saved automatically. Should the drive reverse after reaching the closing 
position (drive opens by approximately 15 mm), a commissioning run must be started. See wiring diagram for IQ 
windowdrives ID 148327. 
With the chain drives Slimchain/Powerchain, the ventilation stroke ex works is limited to 300 mm in the software 
of the drives. In KNX mode, the maximum pre-set ventilation stroke can be approached. The ventilation stroke can 
be adjusted in the drive software via the GEZE ST 220 and the GEZE service case. The maximum ventilation stroke 
is prescribed by the nominal stroke of the drives.

5.2  KNX commissioning

The  KNX bus cable and the 24 V supply must be connected for the commissioning of the IQ box KNX. The drives 
can also be connected subsequently. 

5.2.1  Load ETS product database IQ box KNX

In order to set the parameters of the IQ box KNX via the ETS software (from version 4.0), the product database file 
must be loaded. The ETS product database can be downloaded via the internet from www.geze.com or directly 
from www.iq-box-knx.geze.de.

5.2.2  Assign physical address of the IQ box KNX

From the factory, the IQ box KNX has the physical address 15.15.255. In the KNX-Bus-System, an individual physi-
cal address must be specified for each KNX participant using the ETSasoftware. 
Before or during the programming procedure of the physical address, the KNX programming button (11) of the IQ 
box KNX must be pressed. KNX programming LED turns red. No other KNX participants may be in programming 
mode while assigning the address. 

Содержание IQ box KNX

Страница 1: ...IQ box KNX 166560 00 EN Commissioning manual Prog Ru n...

Страница 2: ...diagram 6 5 Test operation and commissioning of the IQ windowdrives 7 5 1 Test operation 7 5 2 KNX commissioning 7 5 2 1 Load ETS product database IQ box KNX 7 5 2 2 Assign physical address of the IQ...

Страница 3: ...is enclosed with the IQ box KNX and contains the most important product information and instruc tions about the electrical connection and about commissioning of the IQ box KNX IQ windowdrives install...

Страница 4: ...k Ensure that the connection to the power supply is only carried out by a qualified electrician The power con nection and safety earth conductor test must be carried out in accordance DIN VDE 0100 610...

Страница 5: ...4 V external 3 2 2 IQ box KNX top hat rail fitting to top hat rail IQ box KNX top hat rail Power supply NT 1 5 4 2 A 24 V HS GEZE surface housing ID 152010 with 35 mm top hat rail for 6 modules Prog R...

Страница 6: ...mounting wiring diagram 8 9 10 11 12 A B S L GND 24V 33 32 COM A S LIN B S L L A B S A B 230V AC Fenster window 4 24 V DC max 6 A 3 5 7 6 IQ box KNX KNX KNX KNX 1 1 2 4 2 IQ box KNX top hat rail wirin...

Страница 7: ...first time the closing position of the window is detected during the first closing procedure and is saved automatically Should the drive reverse after reaching the closing position drive opens by app...

Страница 8: ...ndow Closed State 1 002 C T 1 Bit OUT T 15 Window Not closed State 1 002 C T 1 Bit OUT T 16 Window Do open State 1 002 C T 1 Bit OUT T 17 Window Do close State 1 002 C T 1 Bit OUT T Alarm 21 Alert Saf...

Страница 9: ...cure windows against jamming a leaf speed of 5 mm s can be required within the framework of a safety analysis Drive noise increases as speeds increase Operation Interval ventilation Settable step widt...

Страница 10: ...lation speed Not suitable for RWA Alarm Wind alarm Rain alarm For wind alarm a binary wind alarm and a wind alarm as threshold value in m s can be selected After the end of the wind rain alarm and a s...

Страница 11: ...time 1 second 5 seconds 10 seconds 30 seconds 1 minute 2 minutes 5 minutes 10 minutes 20 minutes 30 minutes Open window Off time 1 second 5 seconds 10 seconds 30 seconds 1 minute 2 minutes 5 minutes...

Страница 12: ...ventilation Disabled Enabled Window position 0 100 50 4 Window Gap ventilation Trigger Time ventilation Disabled Enabled Window position 0 100 50 5 Window Time ventilation Trigger Ventilation time 5 1...

Страница 13: ...omatic Lock Switch Locked to close Unlock Via object 9 Automatic Lock Switch Until timeout Locking time min 1 300 30 9 Automatic Lock Switch Locked to open and close Unlock Via object 9 Automatic Lock...

Страница 14: ...d state Disabled On change 12 13 14 15 16 17 Window Position between State Window Opened State Window Closed State Window Not closed State Window Do open State Window Do close State Cyclic Cycle time...

Страница 15: ...action on safety alert Close window Open window Type wind alert Binary 23 Alert Wind alert Switch Threshold Threshold windspeed m s 2 30 4 22 Alert Wind speed value m s Behavior after wind rain alert...

Страница 16: ...without self locking Close 32 Button 1 Cl 33 Drive com mand Step Stop Position Window position 0 100 50 33 Button 1 Cl 33 Position Value Button 2 Cl 32 Disabled Lokal Drive type Tip op eration with se...

Страница 17: ...ion Disabled On change 41 Service Check unit State Error information Disabled Error unit Send condition On change 42 Service Error unit State Cyclic Cycle time min 1 255 50 Error collection Send condi...

Страница 18: ...n group Local push button Expanded function examples KNX Easy ventilation controls All basic functions can be realised through the grouping of several windows centrally for the entire ventilation grou...

Страница 19: ...tion examples KNX Automatic closing when the air conditioning is activated If the air conditioning is activated the windows are closed automatically Blocking of the manual opening As long as the air c...

Страница 20: ...idity are exceeded intelligent ventilation is ap plied until the air quality returns to the requirements Controls depending on times of day and usage Ventilation at certain times depending on room us...

Страница 21: ...ox KNX Check length of the connection cable to the drive The overall cable length between IQ box KNX and window must not exceed max 15 m Check software version of the drives on the identification plat...

Страница 22: ...GEZE IQ Box KNX 22...

Страница 23: ...GEZE IQ Box KNX 23...

Страница 24: ...om cn France GEZE France S A R L E Mail france fr geze com www geze fr Hungary GEZE Hungary Kft E Mail office hungary geze com www geze hu Iberia GEZE Iberia S R L E Mail info geze es www geze es Indi...

Отзывы: