GEZE IQ Box KNX
4
2
Safety notices
ATTENTION
Windows, which can be controlled with the IQ box KNX via the KNX Bus, must not be
used in smoke and heat extraction systems.
Area of use for the IQ box KNX is natural ventilation
CAUTION
For automatically controlled windows, which are fitted at heights below 2.5 m, appropri-
ate safety measures to secure against crush and shearing edges must be taken within
the framework of a safety analysis
To ensure personal safety, it is important to follow these safety instructions.
These instructions must be kept.
à
Before installation, read and observe the enclosed safety notes.
Warranty claims require proper mounting, installation and maintenance in accordance with the manufacturer's
specifications.
à
Only appropriately qualified people may carry out installation, commissioning and maintenance. Unauthorised
modifications to the system release GEZE from liability for any resulting damages.
à
Only use GEZE original parts for repair and service work.
à
Ensure that the connection to the power supply is only carried out by a qualified electrician. The power con-
nection and safety earth conductor test must be carried out in accordance DIN VDE 0100-610.
à
Observe the latest versions of guidelines, standards and country-specific regulations.
à
The safety notices in the IQ windowdrives ID 148327 wiring diagram must be observed!
X
The IQ box KNX must be protected from building dirt and water.
X
The IQ box KNX is a product of the KNX systems and detailed specialist know-how gained through KNX train-
ing is required for the product to be understood.
3
Product overview
3.1 Technical data
Bus voltage KNX
30 V DC SELV *)
Supply voltage IQ box KNX and drives
24 V DC, +/-25%, SELV
*)
Max. current drives
6 A
Induced current intake to KNX-bus
5 mA
Induced current intake to 24V
20 mA
IP rating
IP20
Protection rating
III
Ambient temperature
-5°C…+70°C
Connection cross-section 24V supply and drives
max. 1,5 mm²
Connection cross-section inputs/push buttons,
rigid or flexible without wire-end ferrule
max. 0.5 mm²
KNX-bus connection
KNX supply terminal red/black
Max. cable length for push buttons
30 m
Max. overall cable length for drives (LIN-BUS)
15 m