4
Wiring
NRS 19
Use four-core overall screened cable, e. g. IY(ST)Y x x 0.9 or LIYCY 4 x 0.5 mm².
Max. cable length 50 m.
Connect terminal strip in accordance with wiring diagram,
fig. 10
Tools
n
Screwdriver for slotted screws, size .5, completely insulated according to VDE 0680.
Attention
n
To protect the switching contacts fuse circuit with .5 A (slow blow fuse) or according
to TRD regulations (.0 A for 7 hrs operation).
n
The screen must not make any other electrical contact.
Note
n
Connect screen only to terminals 6 and of the switching controller.
n
The mains voltage is indicated on the name plate.
n
When switching off inductive loads, voltage spikes are produced that may impair the
operation of control and measuring systems. Inductive loads should be provided with
commercial arc suppressor RC combinations, e. g. 0. ΩF/00 W.
Содержание NRS 1-9
Страница 2: ... Diese Seite bleibt absichtlich frei ...
Страница 3: ... Deutsch D Seite 4 21 English Page 22 39 ...
Страница 10: ...10 Technische Daten Fortsetzung Maße Fig 2 Fig 3 D 5 120 75 37 5 158 95 ...
Страница 11: ...11 Aufbau Fig 6 E B C F D D Fig 4 Fig 5 F A NRS 1 9 D D ...
Страница 12: ...12 Funktionselemente NRS 1 9 Fig 7 D G 1 2 3 4 5 6 ...
Страница 15: ...15 H C I B A Einbau Fortsetzung Fig 9 Fig 8 Einbaubeispiele F F D ...
Страница 17: ...17 Elektrischer Anschluss Fortsetzung Anschlussplan Fig 10 D NRS 1 9 NRG 16 36 1 4 3 2 1 4 3 2 ...
Страница 28: ...28 Technical Data continued Dimensions Fig 2 Fig 3 5 120 75 37 5 158 95 ...
Страница 29: ...29 Design NRS 1 9 Fig 6 E B C F D D Fig 4 Fig 5 D F A ...
Страница 30: ...30 Functional Elements NRS 1 9 Fig 7 G 1 2 3 4 5 6 ...
Страница 33: ...33 Installation continued Examples of installation H C I B A Fig 9 Fig 8 F F ...
Страница 35: ...35 Wiring continued Wiring diagram Fig 10 NRS 1 9 NRG 16 36 1 4 3 2 1 4 3 2 ...