23
NRR 2-60 - Installation & Operating Manual -
819693-00
Changing the equipment settings
For operation, you must define the controller group and baud rate for the level controller on code switch
D
Fig. 6
. The desired controller functions are achieved by connecting the different level electrodes and
configuring the URB 60 visual display and operating unit as appropriate.
You must set the same baud rate for all bus participants.
Code switch
D
- sliding switch, white
Configuring the controller group and baud rate
NRR 2-60 level controller
Code switch
D
S1
S2
S3
S4
Configuration
ID
OFF
OFF
Controller group 1 (default)
40
OFF
ON
Controller group 2
45
ON
OFF
Controller group 3
60
ON
ON
Controller group 4
65
OFF
Baud rate 50 kBit/s (default)
ON
Baud rate 250 kBit/s
OFF
Reserve (default)
ON
Reserve
Fig. 10
Configure the level controller as described in the Installation & Operating Manual of the URB 60
visual display and operating unit.
■
■
You can find the latest Installation & Operating Manuals for the system components named
in
Fig. 1
on our website:
http://www.gestra.com/documents/brochures.html