NRR 2-60 - Installation & Operating Manual -
819693-00
Wiring diagram of CAN bus system
Important notes on connecting the CAN bus system
■
■
A dedicated 24 V DC SELV power supply unit that is isolated from connected loads must be used to
supply the SPECTOR
connect system.
■
■
Make sure wiring is in line, not in a star!
■
■
Use a central earth to prevent differences in potential in system parts.
■
◆
Connect the bus line shields to one another all the way along, and connect to the central earthing
point (CEP).
■
■
If two or more system components are connected in a CAN bus network, a 120 Ω terminating resistor
must be connected to the
first
and
last
units between terminals C
L
/C
H
.
■
■
The NRR 2-60 level controller is equipped with an internal terminating resistor.
To activate the internal terminating resistor in the NRR 2-60 level controller, insert a bridge between
the terminals (“Option” and “CH”).
■
■
The CAN bus network must not be interrupted during operation!
If it is, an alarm is triggered.