19
Code switch
n
Level controller NRR 2-52, NRR 2-53
S 2
S 3
Input for connecting level electrode NRG 21-.. or
NRG 26-21
OFF
Input for connecting level transmitter NRGT 26-1 *
ON
Fill control
OFF
Discharge control
ON
grey = factory setting
If you want to change the input or the function, set the switches S2 and S3 of the code switch
n
as
indicated in the following table
Fig. 12
.
Level controller: Changing factory settings
- continued -
Changing function and input for level electrode/transmitter
- continued -
Fig. 13
* When connecting level transmitter NRGT 26-1 set the lower and the upper end of the
measuring range
only
in the transmitter. For this purpose follow the instructions given
in the installation & operating manual for the NRGT 26-1.
Do not change the code switch
n
settings of S1 and S4
!
Attention
Toggle switch, white
Tools
n
Screwdriver, size 3.5 x 100 mm, completely insulated according to VDE 0680-1.
n
Screwdriver, size 2 x 100 mm, completely insulated according to VDE 0680-1.