Commissioning
- continued -
Setting the control parameters for 3-element control (optional)
The buttons for setting the control parameters for 3-element control are only available if the level
controller NRR 2-5.. was factory set as 3-element controller.
Press button
to open the parameter setting window for 3-element control.
To enter the evaluation factor press the green
button. Use the on-screen numberpad to enter
the desired value.
The factor evaluates the influence of the diffe-
rence (steam flowrate - feedwater flowrate) on
the measured level signal.
Screen display 5
Press button
to open the parameter setting window for analogue signal inputs 4-20 mA.
Note
Controlled actual value = level - (steam flowrate - feedwater flowrate) x evaluation factor
(only if steam flowrate - feedwater flowrate > 0)
For each flowrate setting press the green
button. Use the on-screen numberpad to enter
the desired value.
Press button
to go back to screen display 5.
Screen display 6
F
Evaluation factor
G
Controlled actual value, influence of difference
(steam flowrate - feedwater flowrate) has been
evaluated
Key
H
Feedwater flowrate
I
Steam flowrate
I
G
NRR 2-5.
NRR 2-5.
F
H