20
Fig. 7
Valve
opens
MAX LED
red
MIN LED
red
Rotary knob
with
integrated
push-button
OO75
OO75
7-segment
display
Valve
closes
Amber
LED
Operation, alarm and testing
Setting switchpoints and control parameters
Note
n
The NRR 2-50 level controller is only equipped with
one
output contact for limit
indications. Therefore, please define its function (MAX or MIN alarm) using the code
switch
c
.
Fig. 5, 6.
n
The actual value is shown on the 7-segment display.
Setting the MIN/MAX switchpoints
Select parameter AL.Lo, enter and save the desired
percentage.
MIN switchpoint setting between 0-100 %
Select parameter AL.Hi, enter and save the desired
percentage.
MAX switchpoint setting between 0-100 %
Setting the setpoint
Select parameter SP, enter and save the desired
percentage.
Setpoint setting between 0-100 %
Please take the settings for MIN/MAX switchpoints into
consideration.
Setting the proportional band
Select parameter Pb, enter and save the desired
percentage.
Proportional band setting between 0-100 %
Setting the integral action time
Select parameter ti, enter and save the desired
percentage.
Integral action time settings between 0-100 s.
Setting the valve travel time (NRR 2-50 only)
Select parameter tt, enter and save the desired
percentage.
Integral action time settings between 10-600 s.