The following relocations of cables with basic insulation are not permissible:
Mains and control cables in low voltage areas.
n
To prevent the welding together of contacts provide an external slow-blow fuse
T 2.5 A for the output contacts.
n
Provide inductive loads with RC combinations according to manufacturer’s specifica-
tion to ensure interference suppression.
n
Provide an external slow-blow fuse for the compact system: 63 mA for 230 V and
115 V or 150 mA for 24 V.
n
Install an easily accessible disconnecting switch for the compact system in the close
proximity of the equipment (EN 61010-1).
n
Mark respective switch as disconnecting device for the compact system.
Tools
Attention
n
Screwdriver for cross head screws, size 1
n
Screwdriver for slotted screws, size 2.5, completely insulated according to VDE 0680
n
Open-end spanner 17 mm A. F.
Electrical Connection
- continued -