22
Commissioning procedure
Check that the level electrode NRG 26-40 is connected to the associated control unit NRS 2-40 or the
level controller NRR 2-40 according to the wiring diagram.
Fig. 11, 12 + 15
Apply supply voltage to the control unit NRS 2-40 or the level controller NRR 2-40.
Applying supply voltage
The measuring range of the level electrode NRG 26-40 can only be adjusted on the control unit
NRS 2-40 and NRR 2-40 and the control & display unit URB. Please observe the installation manuals for
these devices.
Setting measuring range
When adjusting the measuring range when the system is
cold
, the adjusted measuring
points will shift with rising temperature as a result of the longitudinal expansion of the
electrode rod. Correct the settings accordingly.
Note