Setting the control parameters
Press button to open the parameter setting window for the controller.
For each parameter setting press the green
button. Use the on-screen numberpad to enter
the desired value.
Parameter
Deviation
Continuous blowdown valve
Proportional
band
Pb
larger
large remaining deviation
responds slowly
smaller
small remaining deviation
responds quickly and may open/closes all
the time
Example
Measuring range 0 - 6000 µS/cm
Setpoint SP = 3000 µS/cm
Proportional band Pb = +/- 20% of setpoint = +/- 600 µS/cm
With a measuring range of 0 - 6000 µS/cm and a setpoint of 3000 µS/cm the
proportional band will be +/- 600 µS/cm within a range of 2400 to 3600 µS/cm.
Integral
time
ti
larger
slow correction of deviations
responds slowly
smaller
fast correction of deviations, control
system may tend to overshoot
responds quickly
Neutral zone
(dead band)
C
larger
time-delayed correction of
deviations
will not respond until the deviation exceeds
the neutral band
smaller
fast correction of deviations
Valve travel
time
tt
Adjust the valve travel time specified by the
valve manufacturer.