33
A
Bar chart indication of setpoint [in µS/cm]
B
Bar chart indication of manipulated variable Y
[in %], relative to valve lift of continuous
blowdown valve
C
Dead band
Key
D
Purging pulse
E
Purging duration
F
Manual actuator for continuous
blowdown valve
Commissioning
- continued -
Continuous blowdown valve: Setting the purging pulse and duration
Press button to open the parameter setting window for the continuous blowdown valve.
Screen display 7
To enter the purging pulse
D
and the purging
duration
E
press the green button. Use the on-
screen numberpad to enter the desired time
setting. The new time settings are accepted
after the system is re-started or as soon as the
previous purging pulse is over.
If you do not want the continuous blowdown
valve to be purged automatically, deactivate
the purging pulse by pressing the
key .
Press button to go back to the start window.
Screen display 8
Switch back to automatic
operating mode
and scroll back.
Press button to open the parameter setting window for the continuous blowdown valve.
Press button to switch to manual operating mode.
Calibration of "Valve CLOSED"
(0%): Move
the hand slider downwards until "0"
is indicated in the green button.
Press the key "0 %".
Calibration of "Valve OPEN"
(100%):
Move the hand slider upwards until
"100" is indicated in the green button.
Press the key "100 %".
Or press the green button and enter
100 in the numberpad.
Continuous blowdown valve: Calibrating the potentiometer for indication of valve position
F
LRR 1-5.
LRR 1-5.
D
E