18
Electrical Connection
– continued –
Wiring diagram for conductivity switch LRGS 15-1
1
1
3
L2
2
2
2
L1
3
LRGS 15-1
1
N N
P5
P8
P6
P11
P4
P9
P7
P10
P1
P2
P3
1
3
2 9 10 5 4 11
After the burner is switched off (stand-by operation), L2 must remain live until the actuator has closed
the continuous blowdown valve. L1 and L2 must be connected to an outer conductor of the same
phase.
If no resistance thermometer is connected, the terminal lugs P 6, 7, 10 and 11 remain unassigned.
Fig. 8
Actuator EF 1 / EF 06
Temp.
feeler
Pt 100
μS
ppm
Alarm
Max
ϑ
F1
F2
S1 Disconnector
F1 Fuse for output contact
F2 Fuse for conductivity switch
S1
Operation
Open
Closed