LRR 1-52, LRR 1-53, URB 55 - Installation & Operating Manual -
850645-01
Configuring the conductivity controller
Setting automatic intermittent blowdown
If the function “MIN relay for intermittent blowdown”
is set on the code switch of the conductivity control-
ler (see page 37,
Fig. 19
), you can assign param-
eters using the Automatic Intermittent Blowdown
button.
Open the menu.
Auto / Manual
Switch between automatic intermittent
blowdown and manual mode.
Description of parameters:
Initiate intermittent blowdown
manually
The display lights up orange when
intermittent blowdown is active or has
been initiated manually.
Intermittent blowdown interval (in
hours)
Intermittent blowdown time (in
seconds)
The intermittent blowdown valve is
switched on regularly at set intervals
and opens for the set intermittent
blowdown time.
Intermittent blowdown pulses
Number of pulses
Pulse interval (in seconds)
Set the time between the individual
intermittent blowdown pulses.