Work Modes
GV-AS200 and GV-AS400 Controllers support the four types of Work Modes for door-
access control. By default GV-AS Controller is set to
one-way control
.
•
One-way control:
A door is equipped with one card reader for entry. For example, a
user may swipe a card to open the door of office and push a button to leave from the
same door.
•
Two-way control:
A door is equipped with two card readers. The outer reader is
defined as entry reader and the inner reader is defined as exit reader. For example, a
user may swipe a card to gain access to a laboratory, and swipe a card to exit from the
same door.
•
Mixed control:
A mix of One-Way and Two-Way Control applications. Some doors are
equipped with one card reader for entry and some doors are equipped with two card
readers for entry and exit. For example, a building includes both office and laboratory
applications.
•
One-way traffic:
Two doors are applied for entry and exit separately. For example, in a
parking lot, a user may swipe a card at the entrance and swipe a card again at the exit.
Installation Considerations
1. There are distance limitations for Wiegand and RS-485 communications. Please note:
•
Wiegand interface:
30 meters (98.43 feet)
•
RS-485 interface:
600 meters (1968.50 feet)
•
Recommended cable:
standard 485 cable (a twisted pair of 24 AWG wires)
2. GV-ASManager software is used to manage GV-AS100/GV-AS200/GV-AS400 Controllers.
There is a limit for the number of controllers connected to GV-ASManager based on
communication modes.
•
Through the network
, up to 255 GV-AS100/GV-AS200/GV-AS400 Controllers can
connect to GV-ASManager.
•
Through RS-485 connection
, up to 16 GV-AS100/GV-AS200/GV-AS400 Controllers
can connect to the same COM port on a computer running GV-ASManager.