Scrolling Displays:
Cause:
Solution:
6. "...RANGE IS 1 TO
Display averaging
Enter upper display averaging within
10 SECONDS..."
entered incorrectly
1 to 10 seconds range (sec. 3.5)
7. "...RELAY CARD BAD,
Faulty relay card,
A) Verify relay card is installed
MISSING OR
no relay card, or
(sec. 4.5)
WRONG TYPE..."
wrong relay card
B) Verify correct relay card isinstalled
installed
p/n# 3-9000.440-1 (sec. 4.5)
8. "... RUN QTY MUST
Invalid run quantity
Enter run quantity within 1 to 19999
BE MORE THAN 0..."
(0000) entry
batches (sec. 3.7)
9. "...TIMEBASE RANGE
Invalid timebase
Enter valid timebase option:
IS 1 TO 4..."
entry
1 = seconds, 2 = minutes,
3 = hours, 4 = days (sec. 3.5)
10. "...UNABLE TO
No sensor input or
A) Check sensor wiring (sec. 2.3)
CALCULATE
volume entry error
B) Verify volume entry and volume
K-FACTOR..."
decimal position (sec. 3.6)
C) Repeat auto cal sequence if sensor
input was faulty (sec. 3.6)
30
Operational Messages
Displayed Message:
Cause:
Definition/Solution:
1. "ACCESSED"
Security code
Unit momentarily confirms correct
correctly entered
code entry
2. "CAL" or
Menu key pressed
Unit momentarily confirms setup
"BAT"
during menu access
menu selection
3. "RUN CONT"
Unit set to contin-
Display informs operator that
uous batching mode
continuous batching mode is running
4. "INTERUPT"
Unit power cycled,
A) Press BATCH for batch display
power glitch, brown
when interrupt occurred or
out, or EMI inter-
B) Press FLOW for flow display or
ference while
C) Press RESUME to continue batch
batching
where interrupt occurred or
D) Press any key to cancel message
Содержание +GF+ SIGNET 9020 Intelek-Pro
Страница 2: ......
Страница 3: ...GF SIGNET 9020 Intelek Pro Batch Controller Instruction Manual...
Страница 41: ...Notes...
Страница 42: ...Notes...
Страница 43: ......