When installing a Premium Preheat unit,
the instructions below must be followed:
1) Check that the unit is level.
2) Install airtight water traps in a frost-free location
to compensate the pressure of the valve.
3) The height of the water traps must be at least
100 mm.
4) Ensure that the condensation pipe is inclined
all the way from the unit to the drain.
5) Pour some water into the condensation tray of
the unit to ensure that it flows out freely.
6) If the water trap is fitted in a place where there
is a risk that the temperature drops below
0°C, then an electric heating element with a
thermostat protects it against freezing by
turning on when the temperature drops below
+2°C.
7) Adjustment of supply air and extract air volumes
must be made before the ventilation system
may be taken into use. It is important that there
is a balance between the supply air and extract
air volumes.
8) Closing the ceiling valves etc. is recommended,
until the ventilation system is started up.