15
Optima 310
set-point can be configured to between -15°C and 0°C.
The default setting is -10°C.
Item 35: Supply air volume
When the set-point is ON in item 33, it is recommended
to configure the reduced diffusion air volume to 20%
lower the value configured in item 11. The default setting
is 50%.
Item 36: Extra help functions
Extra help functions with relay 8 can be used for the
following:
If the set-point is configured to 0, a circulation pump
•
can be connected for a solar collector, which will be
controlled as described in item 26.
If the set-point is configured to 1, a circulation pump
•
can be connected for water after-heat surface. The
pump will only run when there is a heat requirement.
If the set-point is configured to 2, the relay is on when
•
the device is running. This can e.g. be used to open
and close the fresh air and exhaust valve.
Item 37 Ground heat exchanger
If an earth heat exchanger is fitted to the device and
menu 27 in item 5 has been selected, it is possible to
configure the lowest temperature at which the earth heat
exchanger shall operate.
The set point can be configured to between 0°C and
10°C.
The default setting is 0°C.
Item 38 Changing temperature scale
The temperature scale can be changed on the sensors
T7, T8 and T9 from -30°C / 70°C to -10°C / 90°C by
removing the 3 jumpers on the main circuit board and
configuring it to ON. If the jumpers are attached, the point
should be configured to OFF. The default setting is OFF
The default setting is OFF