background image

6

Subject to Technical Modifications of GES Energy Small and GES Energy Medium

No water in the siphon = water damage

supply air

extract air

fresh air

exhaust air

50

100

Laying GES Energy

Standing GES Energy

100

50

Duct connection

All duct connections are with a yellow sticker indicating the 

type of ventilation pipe to be connected.

Connect the supply air        :

Duct system from the unit to the supply outlet in the living 

area.

Connect the extract air        :

Duct system from wet rooms to the unit.

Connect the fresh air         :

Duct system from fresh air roof cowls/external grills from or 

the ground collector to the unit.

Connect the exhaust air         :

Duct system from unit to the escaping roof cowls/external

grills.

Condensate drain

The units produce up to 6 litres of condensate per day. It is 

therefore important that the condensate drain is correctly 

executed and that the unit has a slight fall towards the 

condensate drain. 

The condensate drain pipe must be air tight for example by 

bending a copper pipe as an siphon (see sketch to the left). 

Use an armed water hose between the drain connecting 

piece on the unit and the siphon and tightend it in both 

ends with a collar band.

From the siphon and to the internal outlet there must be 

a necessary fall on 1%. The condensate drain must be 

fitted with a water trap as there is negative pressure in the 

chamber in which the condensate tray is mounted.

If the unit is installed in a cold loft space, the condensate 

drain pipe must be insulated to prevent freezing of the 

condensate in the pipe. However, it is recommended that 

the water trap is installed in a heated space below to 

ensure that the water in it does not freeze.

If installation problems make it impossible to secure the 

condensate drain pipe from freezing by insulation, it will be 

necessary to mount a thermostat-controlled heating tape 

round the condensate drain pipe.

Optimal operation is achieved by mounting a 

connector piece Ø 160 mm in each outlet of the 

GES Energy and tighten them with the supplied 

collar bands.

While operating there will be a low pressure in 

the unit it will therefor be neccesary to make 

sure that the height difference is min. 50 mm 

to the water in the siphon.

Содержание GES Energy M

Страница 1: ...erigesvej 6 DK 6100 Haderslev Tel 45 73 53 27 00 salg genvex dk genvex dk GES ENERGY S GES ENERGY M PASSIVE VENTILATION WITH WIRING DIAGRAM FOR OPTIMA 100 AND OPTI MA 250 INSTALLATION MANUAL UK Versio...

Страница 2: ...densate drain 6 Duct system 7 Insulation of ducts in cold loft spaces 7 Insulation of ducts in warm spaces 8 Reheating of supply air 8 Electrical connection 9 Inspection and commissioning of the appli...

Страница 3: ...install a thermostat and electrical heater to prevent freezing when the temperature drops below 2 C 7 Air flow adjustments must be made on both supply and exhaust air sides before use of the machine...

Страница 4: ...4 Subject to Technical Modifications of GES Energy Small and GES Energy Medium GES Energy 1 Installation The GES Energy 1 is supplied in a vertical version as shown or a horizontal version The vertic...

Страница 5: ...n it is necessary to remove the rubber feet and place them on the left site of the unit the bottom A A Visible wall mounts unvisible wall mounts Closet mounting gummif dder som leveret ved vandret mon...

Страница 6: ...as an siphon see sketch to the left Use an armed water hose between the drain connecting piece on the unit and the siphon and tightend it in both ends with a collar band From the siphon and to the in...

Страница 7: ...ust air Insulation of ducts in cold loft spaces In order to exploit the unit s high recovery potential efficiency it is necessary to insulate the ducts correctly Genvex recommends as follows Supply an...

Страница 8: ...om the extract air and supply it to the supply air the supply air will be about 1 4 C colder than the room temperature in the dwelling for the whole winter season If this lower supply temperature is i...

Страница 9: ...out 3 Check that filters are clean may be dirty from installation work 4 Check that the condensate drain is correctly mounted with water trap and is protected from freezing Pour 1 litre water into the...

Страница 10: ...s Switch the unit off on the switch on the control panel or the switch on the electrical panel Open the front doors and remove the filters When the filters have been cleaned replaced close the front d...

Страница 11: ...n off without problems If the condensate drain does not work this could lead to water damage in the dwelling Countercurrent heat exchanger Inspect the countercurrent heat exchanger every year If it is...

Страница 12: ...ract air Possible error Faulty extract air fan Clogged extract air fi lter Fuse on the circuit board is blown Cold supply air Possible error Clogged heat changer Faulty extract air fan Clogged extract...

Страница 13: ...800W COS 1 H6 R10 Water valve Belimo Bypass 230VAC H7 R10 Fan extract air 230VAC H8 R12 ON OFF Bypass 2x230VAC H9 R10 Fan supply air 230VAC bypass H16 R8 AUX relay 230VAC max 20W H17 R9 AUX relay 230V...

Страница 14: ...n Supply air Blue Yellow Water valve EC fan Extract air ON OFF Bypass Brown Brown Blue Blue Yellow green Yellow green Water valve Belimo Bypass Humidity sensor White Red Blue EC fan Supply air Aux rel...

Страница 15: ...Fan Supply Max 1 0A EC Fan Exhaust Max 1 0A Mains 1x230VAC 50Hz MAX Fuse 10A Must be connected to earth Yell Green Yell Green Brown Brown Blue Blue Blue Blue Blue Yellow Yellow Yellow Red 5V GND 5V 1...

Страница 16: ...16 Subject to Technical Modifications of GES Energy Small and GES Energy Medium...

Страница 17: ...imised with the newest technologies Advanced controls ensure that as little energy as possible is used for reaching an optimum level of comfort Today s and future construction place greater and greate...

Отзывы: