BRAIN 17
29
732788 - Rev. A_1
ENGLISH
5.4
TIME LEARNING - SETUP
When the board is powered, if a SETUP has never been performed, or if the board requests it, on the
display
S0
indicates that a SETUP must be performed.
During SETUP, the connected BUS G-WAY accessories are always entered.
The BUS G-WAY encoders entered by the SETUP must always be enabled using the para-
meter
En
(BASIC Programming).
For SETUP, proceed as follows:
During SETUP all safety devices are disabled! Therefore, carry out the operation avoiding
any transit in the leaf movement area.
If a system without an encoder is installed, mechanical stops will be required for the leaves.
1. Enter BASIC programming and go to the parameter
tL
, when F is released
--
--
will appear.
2. Ensure that the gate leaves are closed. Otherwise, proceed as follows:
- Press and hold -/R2 to close leaf 2
- Press and hold +/R1 to close leaf 1
Should pr/R1 and/or -/R2 command opening of the corresponding leaf, cut off power
and, on terminal board J2, invert the phase cables of the corresponding motor (terminals 2-3
for leaf 1 motor and terminals 5-6 for leaf 2 motor).
3. With the gate leaves closed, launch SETUP by pressing and holding
+
and
-
until
S1
begins to
flash on the display (about 3 sec).
4. Release
+
e
-
. Leaf 1 begins its opening movement.
Operation WITHOUT Encoder
Stop movement by sending an OPEN A
pulse as soon as leaf 1 reaches the contact
point.
Operation WITH Encoder
Leaf 1 will stop as soon as it reaches the
contact point. It will in any case be possible
to stop leaf movement at any time and in
the desired point by sending an OPEN A
pulse.
5. On the display
S2
will flash (only if 2 motors have been selected): leaf 2 begins opening.
Operation WITHOUT Encoder
Stop movement by sending an OPEN A
pulse as soon as leaf 2 reaches the contact
point.
Operation WITH Encoder
Leaf 2 will stop as soon as it reaches the
contact point. It will in any case be possible
to stop leaf movement at any time and in
the desired point by sending an OPEN A
pulse.
Steps 4 and 5 with function
FA
FA
:
FA
FA
=
01
01
(the limit switch determines the stopping of motion) the OPEN A pulse for stopping
motion is ignored.
FA
FA
=
02
02
(the limit switch determines the start of deceleration) send an OPEN A pulse only
after involving the opening limit switch.