Sec-4.6
Monitored Reversing Devices
Photocell systems provide entrapment protection when mounted near the doorway in such a way that
the lower portion of an individuals leg will break the photocell beam during normal walking through the
doorway.
WARNING
!
AVERTISSEMENT
!
Les systèmes de cellules photoélectriques fournissent une protection contre le coincement s’ils sont
installés à proximité de la porte de manière à ce que la partie inférieure de la jambe d’un individu puisse
rompre le faisceau de la cellule photoélectrique lors de passages normaux par la porte.
Section 4: Programming
OPEN
CLOSE
STOP
CAL
RUN
SCROLL
SCROLL
SET
CLEAR
ODC STB ON
NOTE:
See ENTRAPMENT PROTECTION Sec-1.5 for approved monitored reversing devices. See Sec- 3 for wiring of
approved monitored sensing devices that can be installed onto the
ODC STB
operator terminals.
NOTE:
Turn this feature ON if monitored reversing device is connected to the operators
ODC STB
terminals. If
using an expansion board for reversing devices, see instructions included with expansion board for additional
menu items.
FIG. 9
1. If operator is in RUN mode, press CAL/RUN key to enter CALIBRATION MODE.
2. Use the SCROLL Key to scroll through the menu until ODC STB>OFF is displayed. Press SET/CLEAR key to
toggle to ODC STB > ON. FIG. 9.
3. Press CAL/RUN to return to run mode, or continue with setting OPEN AND CLOSE MODE programming
on the next page.