background image

 

 

Allow catalyst to dry completely before returning to service.  May be dried in the 
sun. 

DISPOSAL 

 

Individual states and provinces may have established disposal standards.  Please 
adhere to your local regulations. 

INSTALLATION 

 

Installation is the reverse of removal.  

 

BALLASTS 

The ballast supplies power to the lamps.  It is located in the 2006D&L unit, where power 
enters the unit.  If a lamp is unlit and a new lamp attached to the same harness will not 
light, the ballast may be at fault.  If a ballast failure is suspected, contact Genesis Air for 
replacement options. 

FILTERS 

The filters help protect the catalyst and lamps from dirt and debris.  They should be 
inspected and replaced regularly.  Genesis Air recommends MERV-13 or higher filters. 

REPLACEMENT PART NUMBERS AND SCHEDULE 

Lamps, catalyst and ballast should only be replaced by the Genesis Air equivalent.   

  

DESCRIPTION 

GENESIS AIR 

PART NUMBER  

BALLAST 

Advance IUV-2S18-HI-LD 

GA18IUV 

LAMPS 

Philips PL-L 18W/TUV 

UVCHO18W 

FILTER 

8”x 10”x 2” MERV 13 

GA0810213 

CATALYST 

8"x 10"x 2" 

GA08102S 

UV SHIELD 

8"x 10"x 1" 

GA0810UVS 