If the clear plug does not emit any glow, the problem may be in the ballast or 
wiring.  Call your Genesis Air Representative for assistance. 

REMOVAL 

 

Power the Genesis Air unit down using the kill switch or breaker to 
unit. 

 

Open the front grille and remove the air filter and UV shield/catalyst assembly. 

 

Grasp the lamp and rock back and forth gently while pulling steadily upwards.  

BE SURE NOT TO USE FORCE!

   The lamp may burst if it collides with the 

fan. 

DISPOSAL 

 

In most states and provinces, UVGI lamps may be disposed of in the same 
manner as fluorescent lamps.  While UVGI lamps contain a trace amount of 
mercury, the quantity is so minute that disposal is not regulated by federal 
standards (established by the EPA).  Individual states and provinces may have 
established disposal standards.  Please adhere to your local regulations. 

INSTALLATION 

 

Installation is the reverse of removal.  

 

CATALYST 

 

ALL UNITS MUST BE POWERED DOWN BEFORE SERVICING. 

 

ALL MAINTENANCE PERSONNEL MUST WEAR UV PROTECTIVE 
SAFETY GLASSES.  ALL EXPOSED SKIN MUST BE PROTECTED BY UV 
RESISTANT CLOTHING. 

GENERAL 

Genesis Air recommends catalyst replacement every fifteen years to provide an efficient 
system.  As debris and contaminants accumulate on the catalyst, the effectiveness of the 
catalyst is decreased.  The catalyst must be inspected periodically for build up of 
particulate.   

INSPECTION 

 

Turn off power to the 2006D&L unit.  Unplug unit from service. 

 

Open the front grille and remove the air filter and UV shield/catalyst assembly. 

 

If the catalyst appears clean and free of particulate, congratulations!  Otherwise, 
proceed to removal. 

REMOVAL 

 

If the catalyst will be cleaned and reused, keep track of orientation so 
they will be returned from the order they were removed.  This will 
prevent installation problems.  

 

 

Turn off power to the 2006D&L unit.  Unplug unit from service. 

 

Open the front grille and remove the air filter and UV shield/catalyst assembly. 

CLEANING 

 

If the catalyst needs cleaning, remove catalyst panel.  Proceed to a wash bay, mop 
sink or other washing area. 

 

Shake or brush heavy particulate from the catalyst. 

 

Spray catalyst liberally using Nu-Calgon CalClean, Special HD or other suitable 
coil cleaner on catalyst only.  Allow to sit 15 minutes, and then wash off with 
water.   