9.3 Understanding the generator's startup and stop processes:
1
The startup of the generator begins a few seconds after the outage of the power
supply.
2
The system sends a signal to the choke closing the air passage.*
3
The system gives power to starting motor to start up the engine, if engine starts,
the power to starting motors will immediately stop to avoid any gear damage in
starting motor. The maximum working time of the starting motor is 5 seconds. If
the engine was not started after 5 seconds, the stating motor will be disconnected
to prevent overheating.
3.1
if the engine was not started at the first attempt a second attempt will
be performed after a few seconds, repeating the process from point 3.
3.2
if the engine was not started at the second attempt a third and last
attempt will be performed after a few seconds, repeating the process from
point 3.
3.3
if the engine was not started at the third attempt there will not be any
other attempt and the panel light “ATS LAMP” will flash showing there is a
startup failure.
3.4
if the generator does not starts automatically, set the "ATS
SELECTOR" switch to off and attempt to start the equipment with the key
according to chapter 5B.
*The engine has a temperature sensor, if the engine is hot for being working
recently, the choke signal will be annulled.
NOTE:
If you perform continuous auto start attempts for only 1 or 2 minutes it may
cause malfunctions of the temperature sensor as this may indicate some
temperature and will annul the choke even though the engine temperature is not
enough for a startup without the choke assistance.
NOTE:
In low temperature conditions, below 5º C the engine will have much
greater difficulty to start so 3 startup attempts would be insufficient. In this case it
would be necessary an operator to manually startup with a key. We recommend
installing the equipment protected from intense cold to avoid start up failures due
to temperature.
NOTE:
Genergy is not responsible in any way for damages caused to
products or equipment that may arise from the lack of supply by a generator
failure.
DANGER: This equipment is not designed to protect vital equipment
such as (life support equipment, extreme safety equipment or other
equipment that involves a risk to persons or property in cases of lack of
supply.