Troubleshooting

1. My humidifier continues to run.

Check for the following:

•  The valve might be stuck in the "open" position. 
•  Check for wiring errors. 
•  Is the unit sized properly for your home?  If it is rated for a smaller-sized home than the home in which it is 

installed, it will work "overtime" to reach the humidification levels desired. 

•  Check the Vapor Pad

®

. If it is clogged, the pad will reduce the humidifier efficiency. Replace if necessary.

2. My solenoid valve is making a "chatter" noise.

This can be caused by any of the following:

•  The power to the valve is less than 18V AC. 
•  The solenoid is causing a "water hammer condition" thru the water pipes (valve closes quickly and shuts off 

water flow, which in turn creates pressure behind the valve that has no avenue of relief).  You may want to install 
a water hammering device with your plumbing, or contact your local plumber to determine the best solution. 

•  The humidistat is located too close to the humidifier or the by-pass pipe. Your humidistat should be a min. of 

1.5' away or greater. 

•  The humidistat could have a buildup of dust, causing a faulty reading. Clean. 
•  The solenoid valve might be dirty.  Remove, inspect and clean if necessary. 
•  Water supply pressure going to the valve may be too low.
•  The hold down nut on top of the solenoid, as it may be loose. 

3. The humidifier is not raising the humidity levels in my home.

Check for the following:

•  Ensure you have changed / replaced your Vapor Pad

®

 at the proper intervals (once per year) to ensure the 

greatest production of moisture. 

•  Check the setting of your humidistat to ensure it is set higher than current humidity levels in your home (when 

in doubt, turn it all the way to the right at maximum production).  If you don't know what your current humidity 
level is, use an instrument called a thermohygrometer (Model 610; GFI #7065) to measure both heat and 
humidity levels in your home.   

•  Calculate your humidity load (Gallons Per Day - GPD) via our humidity calculator (www.generalfilters.com/

Support). Check to see that your humidifier model is designed to produce the amount of moisture (GPD) you 
need.

•  Have you recently installed hardwood floors? Have you recently remodeled and added on to your home? These 

can both increase your home's demand for humidity. Options include connecting your humidifier to the hot 
water supply (which can increase output by as much as 30%), or installing a new humidifier model that can 
generate more humidity. 

•  The unit is not recommended for heat pumps.
•  Plenum temperatures must meet or exceed 120° F to achieve listed capacities.

4. My humidifier will not turn on.

The following might be occurring:

•  Check to see if your humidifier is plugged in, that the breaker is engaged, and that power to other items from 

the same source is working.

•  Check that the damper knob is in the "OPEN" position.
•  Ensure a fuse has not blown. 
•  Check that connectors are properly inserted in the terminal block.
•  Make sure the furnace is operating in the heat mode.

To ensure your safety and the longevity of your unit, we recommend 
contacting a licensed contractor to perform any repairs or maintenance.

!

Содержание 1042LH

Страница 1: ...ial installation voids warranty Modification or alteration of product parts installation instructions or local safety codes voids warranty Read our full warranty policy at the end of this document Bre...

Страница 2: ...ring The Control 6 Installation Final Steps 7 How the Humidifier Works 7 Maintenance 8 Parts Drawing 8 Trouble Shooting 9 FAQ s 10 Limited Warranty 11 12 Model 1042LH Table of Contents WARNING This sy...

Страница 3: ...re nuts 4 Air pressure switch Model 12500 GFI 7021 5 Current sensing relay Model GA50 GFI 7026 Specifications Model 1042LH Legacy Flow Through Humidifier GFI 5144 Type Flow Through GPD 17 Based on 120...

Страница 4: ...screws in the remaining mounting holes Tighten all 8 screws Install drain pan evaporator pad and distributor trough 3 Install connecting collar Connect by pass pipe to collar and humidifier cabinet U...

Страница 5: ...compression connection to saddle valve outlet 7 Turn handle clockwise to pierce tubing and close saddle valve 8 Turn handle counterclockwise to open saddle valve leave open for several seconds to flu...

Страница 6: ...on the humidistat base and mount the base with four screws Place the thick gasket inside the wall mount base to seal off air entering through the vents Low voltage wire may enter the humidistat under...

Страница 7: ...controlled by the electric solenoid valve The humidistat connected in series with the solenoid provides low voltage control of the humidifier The humidistat is designed for wall mounting in the living...

Страница 8: ...om the solenoid valve Remove the brass strainer body from the solenoid valve Carefully pull the strainer screen 990 17 GFI 7005 from the orifice fitting Clean the mineral deposits from all parts If th...

Страница 9: ...nged replaced your Vapor Pad at the proper intervals once per year to ensure the greatest production of moisture Check the setting of your humidistat to ensure it is set higher than current humidity l...

Страница 10: ...d control water flow If you subject the Vapor Pad to cleaning you usually remove much of the coating and the pad becomes ineffective This reduces the output of the humidifier and increases water consu...

Страница 11: ...placing parts is not covered under this Limited Warranty Shipping charges are not covered by this Limited Warranty Agreements made by third parties that are not listed in this Limited Warranty What is...

Страница 12: ...no event be liable for incidental or consequential damages This limited warranty gives you specific legal rights and you may also have other rights which vary from state to state Some states do not al...

Страница 13: ...le soit niveau Ne pas installer l humidificateur ou le tuyau de d rivation de 15 cm 6 po l endroit o l extr mit de la plaque d obturation d un serpentin refroidisseur pourra restreindre le d bit d air...

Страница 14: ...tuyauterie Raccords de tuyau filet s 1 Tourner la poign e dans le sens horaire pour exposer la tige de perforation et fermer le robinet vanne trier 2 Sceller le filetage du corps de la vanne avec un s...

Страница 15: ...bloc vaporateur L orifice standard 990 16 76 fournira environ 3 5 gal h d eau une pression de ligne d eau de 60 psi Pour des pressions d eau basses 20 40 psi un plus grand orifice 990 16 75 est dispo...

Страница 16: ...e d alimentation en eau de 6 mm 1 4 po de la vanne lectromagn tique Retirer le corps de tamis en laiton P N 990 18 de l lectrovanne Retirer soigneusement le filtre tamis P N 990 17 du raccord de l ori...

Отзывы: