S4000C
2
and release the orange tab, clamping the wire in the terminal. Check the hold of the wire by
GENTLY tugging it to ensure it is locked in.
To connect wiring to the Screw Type terminal block, (Figure 3) use a screwdriver to loosen the
top screw counter clock wise. Insert the wire into the terminal and tighten the top screw clock
wise. Check the hold of the wire by GENTLY tugging it to ensure it is locked in.
Figure 2: Spring Type Terminal Block Operation
Figure 3: Screw Type Terminal Block Operation
NOTE:
Power must remain disconnected until all other wiring connections have been made.
The maximum distance between the Model S4000C and the power supply is 3430 feet or 1040
meters (each cable run should be as short as possible). See Section 9.3.3 for cable length
specifications. C24VDC to TB2, position 9. Connect the ground or common to TB2,
position 8.
The instrument is now ready to operate. Please consult the manual for more information on the
instrument’s many features.
NOTE
: If you have any problems in the set-up or testing of the detector, please refer to the
“Trouble Shooting Section”, or call the factory direct.