1.1   INTRODUCTION

This manual has been prepared especially for the purpose of famil-

iarizing personnel with the design, application, installation, opera-

tion and servicing of the applicable equipment. Read the manual 

carefully and comply with all instructions. This will help to prevent 

accidents or damage to equipment that might otherwise be caused 

by carelessness, incorrect application, or improper procedures.
Every effort has been expended to make sure that the contents 

of this manual are both accurate and current. The manufacturer, 

however, reserves the right to change, alter or otherwise improve 

the product at any time without prior notice.

1.2   EQUIPMENT DESCRIPTION

The LTS transfer switch will provide three major functions.

The first function

 is to provide an automatic transfer switch. 

The automatic transfer switch is used for transferring electrical 

loads from a UTILITY (NORMAL) power source to a GENERATOR 

(STANDBY) power source. Such a transfer of electrical loads 

occurs automatically when (connected to a Generac engine gen-

erator) the UTILITY power source has failed or is at a substantially 

reduced voltage and the GENERATOR source voltage and frequen-

cy have reached an acceptable level. The transfer switch prevents 

electrical feedback between two different power sources (such as 

the UTILITY and GENERATOR sources) and, for that reason, codes 

require it in all standby electrical system installations.

The second function

 is to provide a means to divide up the electri-

cal loads on the electrical system. The electrical loads are to be 

divided into “critical loads” and non-essential loads. The “critical” 

loads are connected to the internal 16 circuit panel board. The 

non-essential electrical loads are to be powered from the load shed 

switch (LSS).
The UTILITY source will supply all electrical loads at all times. 

When the transfer signal is given by the engine generator controller, 

all loads, both critical and non-essential loads, are connected to 

the GENERATOR supply. If the generator is overloaded the LSS will 

operate and disconnect the non-essential loads which results in a 

reduction in the load on the generator. 

The third function

 is a 16 circuit load center to connect the “criti-

cal loads” to. These loads will be normally powered by the UTILITY 

source and will be backed up by the GENERATOR source. The 

Siemens load center is provided with the following Siemens type 

QP circuit breakers; 1-50A 2-pole, 1-40A 2-pole, 1-20A 2-pole, 

5-20A single pole and 5-15A 2-pole circuit breakers. 
The LTS transfer switch is suitable for use as SERVICE ENTRANCE 

EQUIPMENT – UTILITY (NORMAL) source only. The  LTS is only 

SERVICE ENTRANCE rated for the USA. The 200A 2-pole circuit 

breaker provided is the “service disconnect” and is labeled as 

such. An additional disconnect must be readily available for the 

alternate source, unless the alternate source is an accessible gen-

erator and can be shutdown.

1.2.1   TRANSFER SWITCH MECHANISM

These switches (Figure 1.1) are used with a single-phase system, 

when the single-phase NEUTRAL line is to be connected to a 

Neutral Lug and is not to be switched.
Solderless, screw-type terminal lugs are standard.

Switch

Rating

Wire

Range

Conductor Tightening

Torque

200A

#6-250 MCM

275 in-lbs.

This transfer switch is suitable for control of motors, electric dis-

charge lamps, tungsten filament and electric heating equipment 

where the sum of motor full load ampere ratings and the ampere 

ratings of other loads do not exceed the ampere rating of the 

switch and the tungsten load does not exceed 30 percent of the 

switch rating.

Figure 1.1 — Typical ATS Transfer Mechanism

UTILITY
CLOSING
COIL

GENERATOR
CLOSING
COIL

UTILITY LUGS

GENERATOR
LUGS (E1 & E2)

LOAD LUGS (T1 & T2)

This transfer switch is for use in optional standby systems only 

(NEC

®

 Article 702).

This transfer switch is suitable for use on a circuit capable of 

22,000 rms symmetrical amperes, 240 VAC maximum.

1.2.2   UTILITY SERVICE DISCONNECT CIRCUIT BREAKER

The utility service disconnect circuit breaker for the 200 amp 

models are:
•  Generac, Type 225AF, 2-pole
• 120/240VAC, 200A
• 50/60 Hertz
•  Wire range:  300 MCM - 6 STR (Line), 250 MCM - 6 STR (Load)
•  The conductor tightening torque is 375 in-lbs. (Line), 275 in-

lbs. (Non-essential Load and Generator Terminals)

General Information

Содержание RTSJ200A3

Страница 1: ...This manual should remain with the unit Owner s Manual LTS Load Shed Switch...

Страница 2: ...infor mation on tags decals and labels that may be affixed to the transfer switch Replace any decal or label that is no longer legible DANGER Connection of a generator to an electrical system normall...

Страница 3: ...hazardous and possibly LETHAL electric shock DO NOT WORK ON THE TRANSFER SWITCH UNTIL ALL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF Competent qualified personnel should inst...

Страница 4: ...will operate and disconnect the non essential loads which results in a reduction in the load on the generator The third function is a 16 circuit load center to connect the criti cal loads to These lo...

Страница 5: ...switches 1 4 For one shot operation mode set DIP switch 5 to ON Reconnection of the non essential loads will occur one time after the time set on DIP switches 1 4 If DIP switch 5 is OFF the LSC will a...

Страница 6: ...stalling Do not drop the switch Protect the switch against impact at all times and against construction grit and metal chips Never install a transfer switch that has been damaged This transfer switch...

Страница 7: ...rals are to be connected on the busbars mounted on the load center next to the branch circuit breakers 2 6 CONNECTING CONTROL WIRES Control system interconnections consist of N1 N2 and T1 and leads 0...

Страница 8: ...L position no further action is required If the handle is DOWN proceed with Step 1 Step 1 With the handle inserted into the moveable contact carrier arm move handle UP Be sure to hold on to the handle...

Страница 9: ...NOW BEING DELIVERED TO TRANSFER SWITCH TERMINALS CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRICAL SHOCK 7 With an accurate AC voltmeter and frequency meter chec...

Страница 10: ...ual Operation Handle and operating lever of transfer switch should be in UP position 10 Turn on the UTILITY power supply to transfer switch using the UTILITY SERVICE DISCONNECT circuit breaker The uti...

Страница 11: ...9 Notes...

Страница 12: ...10 Notes...

Страница 13: ...11 Notes...

Страница 14: ...12 Installation Diagram 200 Amp Enclosure Drawing 0G8775 B...

Страница 15: ...8 9 B 2 1 3 9 8 7 B D1 A 6 3 4 5 2 1 7 6 3 2 1 4 5 1 2 2 1 3 1 2 3 4 5 6 J4 RL2 D2 1 2 2 1 3 TO LOADS NON ESSENTIAL TOP TERMINALS TO GROUNDING ELECTRODE 194 OPTIONAL ALARM CONTACT CUSTOMER SUPPLIED N...

Страница 16: ...Part No 0H8807 Revision E 08 01 13 Printed in U S A...

Отзывы: