Operation

14

Automatic Transfer Switch Owner’s Manual

Close to Generator Source Side

See 

Figure 4-1

. Before proceeding, verify the position of

the switch by observing the position of the manual
operation handle. If the handle is DOWN, the contacts
are closed in the GENERATOR (STANDBY) position. No
further action is required. If the handle is UP, proceed
with Step 1.

1.

With the handle inserted into the movable contact
carrier arm (A), move the handle DOWN. Be sure
to hold on to the handle as it will move quickly after
the center of travel.

2.

Remove manual operating handle from movable
contact carrier arm. Return manual operating
handle to storage bracket (B).

Return to Utility Source Side

1.

Manually actuate switch to return manual operating
handle to the UP position.

2.

Remove manual operating handle from movable
contact carrier arm. Return manual operating
handle to storage bracket (B).

Voltage Checks

Utility Voltage Checks

1.

Turn ON the UTILITY power supply to the transfer
switch using the utility service disconnect circuit
breaker.

2.

With an accurate AC voltmeter, check for correct
voltage. Measure across ATS terminal lugs N1 and
N2; N1 to NEUTRAL and N2 to NEUTRAL.

Generator Voltage Checks

1.

On the generator panel, select the MANUAL mode
of operation. The generator should crank and start.

2.

Let the generator stabilize and warm up at no-load
for at least five minutes.

3.

Set the generator's main circuit breaker (CB1) to its
ON or CLOSED position.

4.

With an accurate AC voltmeter and frequency
meter, check the no-load, voltage and frequency.
Measure across ATS terminal lugs E1 to E2; E1 to
NEUTRAL and E2 to NEUTRAL.

5.

When certain that generator supply voltage is correct
and compatible with transfer switch ratings, turn OFF
the generator supply to the transfer switch.

6.

On the generator panel, select the OFF mode to
shut down the generator.

NOTE: Do NOT proceed until generator AC output
voltage and frequency are correct and within stated
limits. If the no-load voltage is correct but no-load
frequency is incorrect, the engine governed speed
may require adjustment. If no-load frequency is
correct but voltage is not, the voltage regulator may
require adjustment.

Generator Tests Under Load

1.

Set the generator main circuit breaker to OFF or
OPEN.

2.

Set the utility service disconnect circuit breaker to
OFF or OPEN.

3.

Manually actuate the transfer switch main contacts
to the emergency (Standby) position. See “Manual
Operation”.

4.

To start the generator, select the MANUAL mode of
operation. When engine starts, let it stabilize for a
few minutes.

5.

Set the generator main circuit breaker to ON or
CLOSED. The generator now powers all LOAD
circuits. Check generator operation under load as
follows:

Turn on electrical loads to the full rated
wattage/amperage capacity of the generator.
DO NOT OVERLOAD.

With maximum rated load applied, check
voltage and frequency across transfer switch
terminals E1 and E2. Voltage should be
greater than 230 VAC (240 VAC system);
frequency should be greater than 59 Hz.

(000129)

DANGER

Electrocution. High voltage is present at 
transfer switch and terminals. Contact with live 
terminals will result in death or serious injury.

 

(000123)

DANGER

Electrocution. Turn utility supply OFF before 
working on utility connections of the transfer 
switch. Failure to do so will result in 
death or serious injury.

 

Frequency

60-62 Hz

Terminals E1 to E2

240-246 VAC

Terminals E1 to NEUTRAL

120-123 VAC

Terminals E2 to NEUTRAL

120-123 VAC

(000129)

DANGER

Electrocution. High voltage is present at 
transfer switch and terminals. Contact with live 
terminals will result in death or serious injury.

 

Содержание RTG24SHA1

Страница 1: ...1 100A RTG42SHA1 200A Register your Generac product at WWW GENERAC COM 888 436 3722 Para espa ol visita http www generac com service support product support lookup SAVE THIS MANUAL FOR FUTURE REFERENC...

Страница 2: ...contains or emits chemicals known to the state of California to cause cancer birth defects and other reproductive harm 000004 WARNING California Proposition 65 Engine exhaust and some of its constitue...

Страница 3: ...y Source Side 13 Close to Generator Source Side 14 Return to Utility Source Side 14 Voltage Checks 14 Utility Voltage Checks 14 Generator Voltage Checks 14 Generator Tests Under Load 14 Checking Autom...

Страница 4: ...Table of Contents iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...ible circumstance that might involve a hazard The warnings in this manual and on tags and decals affixed to the unit are therefore not all inclusive If using a procedure work method or operating techn...

Страница 6: ...connections of the transfer switch Failure to do so will result in death or serious injury 000157 DANGER Electrocution Do not disable or modify the connection box door safety switch Doing so will res...

Страница 7: ...ch Failure to do so will result in death or serious injury 000104 DANGER Electrocution Water contact with a power source if not avoided will result in death or serious injury 000188 DANGER Electrocuti...

Страница 8: ...Introduction and Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...standby electric system installations The transfer switch consists of a transfer mechanism utility service disconnect circuit breaker a control relay fuses terminal strip and fuse holder for connecti...

Страница 10: ...Code UL 1008 STANDARD FOR SAFETY AUTOMATIC TRANSFER SWITCHES UL 67 Panelboards Marking and Application Guide NOTE It is essential to use the latest version of any standard to ensure correct and curre...

Страница 11: ...termined by generator frequency Loads are shed when frequency is less than 58 Hz for three seconds or less than 50 Hz for one half second for 60 Hz systems The SACM can be used in conjunction with ind...

Страница 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 13: ...onvenience and proximity to the utility supply and load center Install the transfer switch as close as possible to the electrical loads that are to be connected to it Mount the switch vertically to a...

Страница 14: ...NEC Article 210 4 Connecting Power Source and Generator Power Supply Installation and interconnection diagrams are provided in this manual NOTE All installations must comply with national state and l...

Страница 15: ...wiring connection details Recommended wire gauge sizes for this wiring depends on the length of the wire as recommended in the following chart Exception Conductors of AC and DC circuits rated 1000 vol...

Страница 16: ...is in utility mode The contacts will open when the transfer switch is in the standby power mode Figure 3 5 Auxiliary Contact NOTE Auxiliary Contact is rated 10 amps at 125 or 250 volts AC and 0 6 amp...

Страница 17: ...sm main contacts by observing the movable contact carrier arm This can be viewed through the long narrow slot in the inside cover of the ATS The top of the movable contact carrier arm is yellow to be...

Страница 18: ...nsfer switch ratings turn OFF the generator supply to the transfer switch 6 On the generator panel select the OFF mode to shut down the generator NOTE Do NOT proceed until generator AC output voltage...

Страница 19: ...utility power source Approximately one minute after re transfer the engine should shut down With the generator in the AUTOMATIC mode the system is now set for fully automatic operation Installation S...

Страница 20: ...Operation 16 Automatic Transfer Switch Owner s Manual Testing The Smart Management Module Refer to the SMM Owner s Installation Manual for testing that product...

Страница 21: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 17 Section 5 Drawings and Diagrams Installation Drawings Installation Drawing No 10000005900 100A 2 of 2...

Страница 22: ...Drawings and Diagrams 18 Automatic Transfer Switch Owner s Manual Installation Drawing No 10000005900 200A 1 of 2...

Страница 23: ...Transfer Switch Owner s Manual 19 Interconnection Drawings Interconnection Drawing 10000005901 Air Cooled 100A Generator page 1 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG24SHA1 DRAWING 1000...

Страница 24: ...s 20 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005901 Air Cooled 100A Generator page 2 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG24SHA1 DRAWING 10000005901 REVIS...

Страница 25: ...s Automatic Transfer Switch Owner s Manual 21 Interconnection Drawing 10000005901 Air Cooled 200A Generator page 1 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG42SHA1 DRAWING 10000005901 REVIS...

Страница 26: ...ms 22 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005901 Air Cooled 200A Generator page 2 of 2 INTERCONNECTION DRAWING AIR COOLED GENERATOR RTG42SHA1 DRAWING 10000005901 REVI...

Страница 27: ...utomatic Transfer Switch Owner s Manual 23 Interconnection Drawing 10000005855 Liquid Cooled 100A Generator page 1 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG24SHA1 DRAWING 10000005855 RE...

Страница 28: ...4 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005855 Liquid Cooled 100A Generator page 2 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG24SHA1 DRAWING 10000005855 RE...

Страница 29: ...utomatic Transfer Switch Owner s Manual 25 Interconnection Drawing 10000005855 Liquid Cooled 200A Generator page 1 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG42SHA1 DRAWING 10000005855 RE...

Страница 30: ...6 Automatic Transfer Switch Owner s Manual Interconnection Drawing 10000005855 Liquid Cooled 200A Generator page 2 of 2 INTERCONNECTION DRAWING LIQUID COOLED GENERATOR RTG42SHA1 DRAWING 10000005855 RE...

Страница 31: ......

Страница 32: ...rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W2929...

Отзывы: